| Plan Review Notes For Permit 19080673 |
| Permit Number |
19080673 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-08-23 12:38:04 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) SHEET E 201 - THERE IS AN INDICATION OF FIRE ALARM | | | DEVICE RELOCATIONS. | | | | | | ANY FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE PERMIT | | | AND SHOP DRAWINGS, | | | | | | | | | | | | 2) SHEET A 02 - THE INSTALLATION OF THE LARGE PROJECTOR | | | MAY OBSTRUCT FIRE SPRINKER HEADS SPARY PATTERNS. | | | | | | PLEASE REVIEW WITH FIRE SPRINKLER CONTRACTOR FOR CODE | | | COMPLIANT COVERAGE. | | | | | | ANY REQUIRED WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE | | | DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|