| Plan Review Notes For Permit 19080660 |
| Permit Number |
19080660 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-08-13 14:42:47 | 1) THE GAS SIZING TABLE FOR THE CSST REFERENCED ON THE | | | GAS DRAWING, 402.4 (16), IS FOR A GAS PRESSURE LESS | | | THAN 2 PSI BUT THE GAS DRAWING IS SHOWING A 2 PSI | | | SYSTEM. CLARIFY. SUBMIT TWO COPIES OF THE CORRECT | | | SIZING TABLES OR PLACE A NOTE ON THE DRAWING SPECIFYING | | | WHICH SIZING TABLE(S) FROM THE GAS CODE OR OTHER | | | STANDARD ARE BEING USED IN THE DESIGN OF THIS SYSTEM. | | | 2) THE SUBMITTED GAS DRAWING IS REFERENCING TWO | | | DIFFERENT GAS SIZING TABLES, ONE FOR SCH. 40 METALLIC | | | PIPE AND ONE FOR CSST. WHICH IS IT? CLARIFY. | | | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS AND | | | INSTALLATION INSTRUCTIONS FOR THE REGULATORS. WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 4) WHERE CONNECTED TO RIDGID PIPING, A UNION IS | | | REQUIRED WITHIN ONE FOOT OF EITHER SIDE OF THE MP | | | REGULATOR. 2017 FBC-FUEL GAS SEC.410.2 (7). | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|