Plan Review Notes
Plan Review Notes For Permit 19080609
Permit Number 19080609
Review Stop B
Sequence Number 1
Notes
Date Text
2019-08-13 12:18:02JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 YOU MAY RESUBMIT UP TO TWO PAGES, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 1.FBC B 107.2.1. PLEASE CORRECT THE FOLLOWING; ON THE
 SCHEDULE FOR INSTALLATION OF PROTECTIVE DEVICES OR
 ASSEMBLIES: COLUMN HEADING ?ANCHOR SPACING?; VERIFY
 INFORMATION FROM PAGE 12 OF PRODUCT APPROVAL FL1850;
 EXAMPLE: CONNECTION TYPE D WALL SILL MOUNTING
 INSTALLATION FOR CONCRETE, MAXIMUM SHUTTER SPAN 10?-0?
 DESIGN NEGATIVE LOAD 60 PSI, SYSTEM COMPONENT 14 USING
 TAPCON WITH ADVANCED THREADFORM TECHNOLOGY ANCHOR
 SPACING IS 5.5?; YOU MUST ALSO MULTIPLY THE ANCHOR
 SPACING GIVEN BY THE FACTOR OF .9 TO ACHIEVE THE
 CORRECT ANCHOR SPACING.
  