| Plan Review Notes For Permit 19080544 |
| Permit Number |
19080544 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2020-04-24 12:52:11 | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) NO RISER DIAGRAM SHOWN SHOWING THE WIRE SIZES AND | | | BREAKER SIZES. 215.5 | | | | | | 2) SHOW SERVICE GROUNDING 250.32 | | | |
|