| 2019-12-17 14:19:08 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | NFPA 99 = HEALTH CARE FACILITIES CODE |
| | NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 2ND REVIEW |
| | |
| | GAS COMMENTS: DENIED |
| | |
| | REGARDING PAST REVIEW DATED 10/23/2019 |
| | 1. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, |
| | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING |
| | AND/OR SYSTEM PER THE FBC-2017 FUEL GAS APPENDIX A; USE |
| | OF CAPACITY SECTION A.3.1(4) & 2017 FUEL GAS CODE SEC. |
| | 402.4.1. |
| | REGARDING COMMENT #1; PER WPB FBC 107.2.1 AND |
| | 107.3.5.3(13), OUTLET FOR FUTURE BBQ SHALL BE INCLUDED |
| | IN CALCULATIONS. CALCULATIONS BASED ON FBC FG TABLE |
| | 402.4(2) MAXIMUM 90? POINT OF DELIVERY TO FARTHEST |
| | OUTLET. THEREFORE, THE BRANCH TO THE FUTURE BBQ OUTLET |
| | AT 120CFH IS UNDERSIZED. |
| | 2. COMPLIED |
| | 3. SECOND REQUEST: SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, LENGTH, SIZE AND TERMINATION OF THE GAS VENTS |
| | PER FBC-2017 FUEL GAS CODE SEC. 502 THRU 505. |
| | ADDITIONAL COMMENT: THIS APPLIES TO THE LINEAR GAS |
| | FIREPLACE AND IF LOCATED INDOORS, THE GAS TANKLESS |
| | WATER HEATERS. |
| | 4. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL |
| | GAS EQUIPMENT AND REGULATORS TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND FBC-2017 FUEL GAS SEC. |
| | 402.2 |
| | REGARDING COMMENT #4 FROM LAST REVIEW; PER WPB FBC |
| | 107.2.1 AND 107.3.5.3(13), THE MANUFACTURER?S |
| | SPECIFICATION SHEETS PROVIDED AS REQUIRED BY WPB FBC |
| | 107.2.1 AND 107.3.5.3(13) ARE INCOMPLETE. PER WPB FBC |
| | 107.2.1 AND WPB FBC AND 107.3.5.3(13), PROVIDE THE |
| | MANUFACTURER?S SPECIFICATION SHEETS FOR ALL GAS FIRED |
| | EQUIPMENT AND APPLIANCES. INFORMATION PROVIDED SHALL |
| | INCLUDE BUT NOT BE LIMITED TO MODEL NUMBER, BTU INPUT, |
| | FUEL TYPE, VENTING REQUIREMENTS/CONNECTIONS WHERE |
| | APPLICABLE, GAS CONNECTION LOCATION AND SIZE AND |
| | MAXIMUM PRESSURE INLET REQUIREMENTS. INCLUDE |
| | REGULATORS, DRYER, COOKTOP, LINEAR GAS FIREPLACE, |
| | FUTURE BBQ AND TANKLESS WATER HEATERS. SHOW OUTDOOR |
| | RATING IF APPLICABLE. BTU INPUT ON SUBMITTALS SHALL |
| | MATCH INFORMATION NOTED ON THE PLAN. |
| | 5. COMPLIED |
| | 6. COMPLIED |
| | |
| | NEW COMMENTS: |
| | 1. SHOW LOCATIONS OF TANKLESS WATER HEATERS ON THE |
| | FLOOR PLAN. |
| | 2. PROVIDE LOCATION OF FUTURE BBQ GRILL ON FLOOR PLAN |
| | 3. REGARDING REGULATORS INSTALLED INDOORS, IF VENT |
| | ELIMINATORS ARE TO BE USED IN LIEU OF VENT PIPING TO |
| | EXTERIOR, PROVIDE A NOTE STATING SUCH AND PROVIDE A |
| | MANUFACTURER?S SPECIFICATION SHEET FOR THE VENT |
| | ELIMINATOR. CONFIRM THE SUBMITTED REGULATOR AND VENT |
| | ELIMINATOR ARE COMPATIBLE. OTHERWISE, PROVIDE VENT PIPE |
| | ROUTING, SIZE, TERMINATION AND MATERIAL FOR VENTS TO |
| | THE OUTSIDE. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19080511 215 9TH ST |
| | |
| | |
| | |