2019-10-23 10:07:571ST REVIEW: 19080511
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS:
  
 1. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2017 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2017 FUEL GAS CODE
 SEC. 402.4.1.
  
 2. PLEASE SHOW METER ON FLOOR PLAN. PER WPB AMEND TO
 FBC 107.2.1
  
 3. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, LENGTH,
 SIZE AND TERMINATION OF THE GAS VENTS PER FBC-2017 FUEL
 GAS CODE SEC. 502 THRU 505.
  
 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT AND REGULATORS TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2017 FUEL GAS SEC.
 402.2
  
 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2017 FUEL GAS CODE SEC. 304.
  
 6. PROVIDE SIZING TABLES USED FOR SIZING SYSTEM . PER
 FBC FG SEC 402.4 TABLES 402.4(1)- 402.4(37)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  