| 2019-10-23 10:07:57 | 1ST REVIEW: 19080511 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | GAS COMMENTS: |
| | |
| | 1. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, |
| | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING |
| | AND/OR SYSTEM PER THE FBC-2017 FUEL GAS APPENDIX A ? |
| | USE OF CAPACITY SECTION A.3.1(4) & 2017 FUEL GAS CODE |
| | SEC. 402.4.1. |
| | |
| | 2. PLEASE SHOW METER ON FLOOR PLAN. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | 3. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, LENGTH, |
| | SIZE AND TERMINATION OF THE GAS VENTS PER FBC-2017 FUEL |
| | GAS CODE SEC. 502 THRU 505. |
| | |
| | 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL |
| | GAS EQUIPMENT AND REGULATORS TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND FBC-2017 FUEL GAS SEC. |
| | 402.2 |
| | |
| | 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| | FBC-2017 FUEL GAS CODE SEC. 304. |
| | |
| | 6. PROVIDE SIZING TABLES USED FOR SIZING SYSTEM . PER |
| | FBC FG SEC 402.4 TABLES 402.4(1)- 402.4(37) |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |