| Plan Review Notes For Permit 19080511 |
| Permit Number |
19080511 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-10-31 15:41:37 | APPROVED WITH PROVISO ON PLAN FOR FEEDER SIZES, WIRE TO | | | FPL MUST BE SIZED FOR 350 AMP SERVICE PER NEC | | | 310.15(B)(7) AND FBC RE E3603.1.1. WIRE FROM METER TO | | | PANELS MUST BE SIZED PER NEC 310.15(B)(16) AND FBC RE | | | E3704.1 |
|