Plan Review Notes
Plan Review Notes For Permit 19080511
Permit Number 19080511
Review Stop E
Sequence Number 2
Notes
Date Text
2019-10-31 15:41:37APPROVED WITH PROVISO ON PLAN FOR FEEDER SIZES, WIRE TO
 FPL MUST BE SIZED FOR 350 AMP SERVICE PER NEC
 310.15(B)(7) AND FBC RE E3603.1.1. WIRE FROM METER TO
 PANELS MUST BE SIZED PER NEC 310.15(B)(16) AND FBC RE
 E3704.1