Plan Review Notes
Plan Review Notes For Permit 19080511
Permit Number 19080511
Review Stop B
Sequence Number 2
Notes
Date Text
2019-10-21 10:44:58BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19080511
 1ST REVIEW: SEPTEMBER 17, 2019
 2ND REVIEW: OCTOBER 21, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
 FEMA P-758
  
 1. 501.1.1 FBC[RE] ADDITIONS, ALTERATIONS, OR REPAIRS:
 GENERAL. ADDITIONS, ALTERATIONS, OR REPAIRS TO AN
 EXISTING BUILDING, BUILDING SYSTEM OR PORTION THEREOF
 SHALL COMPLY WITH SECTION R502, R503 OR R504. UNALTERED
 PORTIONS OF THE EXISTING BUILDING OR BUILDING SUPPLY
 SYSTEM SHALL NOT BE REQUIRED TO COMPLY WITH THIS CODE.
 - PROVIDE DOCUMENTATION OF ENERGY CODE COMPLIANCE FOR
 THE METHOD CHOSEN.
 2 ND REVIEW ADDITIONAL COMMENT.
 NO DOCUMENTATION PROVIDED TO SHOW COMPLIANCE WITH
 ENERGY CODE. PLEASE REVIEW COMMENT 1 AND PROVIDE
 DOCUMENTATION FOR THE COMPLIANCE METHOD CHOSEN.
  
 2. OK.
  
 3. OK.
  
 4. OK.
  
 5. OK.
  
 6. 322.2.2 FBC[R] ENCLOSED AREAS BELOW DESIGN FLOOD
 ELEVATION.
 - AREAS THAT ARE BELOW B.F.E. ,AND MEET THE
 REQUIREMENTS OF R322.2.2 (1), NEED TO BE DESIGNED WITH
 FLOOD OPENINGS AS OUTLINED IN R322.2.2 (2).
  
 R322.2.2 ENCLOSED AREA BELOW DESIGN FLOOD ELEVATION.
 ENCLOSED AREAS, INCLUDING CRAWL SPACES, THAT ARE BELOW
 THE DESIGN FLOOD ELEVATION SHALL: (SEE R322.2.2 FOR
 REQUIREMENTS)
  
 R322.2.2.1 INSTALLATION OF OPENINGS. THE WALLS OF
 ENCLOSED AREAS SHALL HAVE OPENINGS INSTALLED SUCH THAT:
 (SEE R322.2.2 FOR REQUIREMENTS)
  
  
 7. OK.
  
 WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  