| 2020-06-24 08:47:12 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| | PART VIII ELECTRICAL |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | 1) SEPARATE STRUCTURE (GARAGE) TO HAVE A PANEL |
| | INSTALLED BECAUSE OF THE NUMBER OF BRANCH CIRCUITS |
| | INSTALLED, SEE 225.30 |
| | |
| | 225.30 NUMBER OF SUPPLIES A BUILDING OR OTHER STRUCTURE |
| | THAT IS SERVED BY A BRANCH CIRCUIT OR FEEDER ON THE |
| | LOAD SIDE OF A SERVICE DISCONNECTING MEANS SHALL BE |
| | SUPPLIED BY ONLY ONE FEEDER OR BRANCH CIRCUIT UNLESS |
| | PERMITTED IN 225.30(A) THROUGH (E). FOR THE PURPOSE OF |
| | THIS SECTION, A MULTIWIRE BRANCH CIRCUIT SHALL BE |
| | CONSIDERED A SINGLE CIRCUIT. |
| | |
| | 2) SEPARATE STRUCTURES TO HAVE GROUNDING ELECTRODE |
| | SYSTEMS INSTALLED, SEE 250.32 |
| | |
| | 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY A FEEDER(S) |
| | OR BRANCH CIRCUIT(S) (A) GROUNDING ELECTRODE. |
| | BUILDING(S) OR STRUCTURE(S) SUPPLIED BY FEEDER(S) OR |
| | BRANCH CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE OR |
| | GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE WITH |
| | PART III OF ARTICLE 250 |
| | |
| | 3) PANEL SCHEDULE REQUIRED FOR NEW PANEL IN GARGE. |
| | |