| 2020-05-05 13:30:28 | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | |
| | PLAN REVIEW - PLUMBING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER ? BUILDING - PX3169 |
| | PLANS EXAMINER ? 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 2ND REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. |
| | PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED |
| | SATISFACTORILY HAVE ADDITIONAL COMMENTS IN PARENTHESES. |
| | ANY NEW COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. PLEASE PROVIDE MANUFACTURES SPECIFICATION FOR INSTA |
| | HOT PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1. |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. (NOT ADDRESSED) |
| | |
| | 2. PLUMBING RISER DIAGRAM REQUIRED PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.3.5.3 (11) RESIDENTIAL |
| | PLUMBING. (NOT ADDRESSED) |
| | |
| | 3. BACKFLOW PREVENTER FOR IRRIGATION AND MAIN SERVICE |
| | REQUIRED PER THE CITY OF WEST PALM BEACH ORD #2853-95. |
| | A PERMIT REQUIRED BY A LICENSED CONTRACTOR AND MUST BE |
| | CERTIFIED BY UTILITIES PRIOR TO FINAL INSPECTION. |
| | PLEASE CONTACT CITY OF WPB UTILITIES AT 561-822-2240 |
| | FOR FURTHER DIRECTIONS. (NOT ADDRESSED) |
| | |
| | NEW COMMENT: |
| | |
| | 1. PROVIDE WATER DISTRIBUTION DIAGRAHM. |
| | |
| | P2903.1WATER SUPPLY SYSTEM DESIGN CRITERIA. |
| | THE WATER SERVICE AND WATER DISTRIBUTION SYSTEMS SHALL |
| | BE DESIGNED, AND PIPE SIZES SHALL BE SELECTED SUCH THAT |
| | UNDER CONDITIONS OF PEAK DEMAND, THE CAPACITIES AT THE |
| | POINT OF OUTLET DISCHARGE SHALL NOT BE LESS THAN SHOWN |
| | IN TABLE P2903.1. |
| | |