| Notes |
| Date |
Text |
| 2019-08-30 13:28:30 | PLUMBING 1ST REVIEW**DENIED** | | | | | | 1-ALL PLANS SHALL BE SIGNED BY PERSON DESIGNING AND | | | TAKING RESPONSIBILITY. FS 471, 481, 489 | | | 2-PROVIDE COMPLETE CABINET HEIGHT DETAIL SHOWING MAX | | | 34?. FBC-ACC212, 606.2, 804.3.2 | | | 3- PROVIDE APPLIANCE DETAIL SHOWING ALL REACH RANGES | | | COMPLY. FBC-ACC 804.3.2 | | | 4- PROVIDE SANITARY AND WATER ISOMETRIC DRAWING. FBC | | | 107.3.5 | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH ( CGA SOLUTIONS) | | | [email protected] | | | 561-248-2703 | | | |
|