2019-08-28 05:59:21ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. UNABLE TO COMPLETE REVIEW. NOTES ON PLAN FROM P.E.
 DENNIS J. HERGENRETHER LICENSE #73535 "PLANS HAVE BEEN
 RELEASED FOR INTERIM REVIEW ONLY AND ARE NOT TO BE USED
 FOR CONSTRUCTION, BIDDING, OR PERMITTING.
  
 2. PERMIT APPLICATION SAYS "LOW VOLTAGE" ONLY. PLEASE
 BE MORE SPECIFIC IN THE DESCRIPTION. WHICH LOW VOLTAGE
 SYSTEMS ARE TO BE INSTALLED IN THIS SCOPE OF WORK? FBC
 107.2.1
  
 3. PROVIDE CUT SHEETS FOR PRODUCT APPROVAL OF ALL LOW
 VOLTAGE DEVICES. FBC 107.2.1 NEC 90.7,110.2, 110.3B
  
 4. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  