| 2019-09-05 09:14:44 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS |
| | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC |
| | 109.3 |
| | 2. LOAD CALCULATION SHOWS A LOAD OF 223 AMPS ON |
| | SERVICE. RISER DIAGRAM SHOWS DISCONNECT AND PANEL RATED |
| | FOR 200 AMPS. PROVIDE CORRECTION. NEC 215.2, 408.30, |
| | 408.36; WPB FBC 107.3.5; FBC RE E3602.3 |
| | 3. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| | SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| | KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| | PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| | RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| | SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE |
| | CORRECTION. NEC 210.12; FBC RE E3902.16 |
| | 4. ALL RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS |
| | SHALL HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC |
| | 210.8(A)(9); FBC RE E3902.9 |
| | 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| | 210.8(D); FBC RE E3902.10 |
| | 6. PROVIDE LOCATION OF ELECTRICAL SERVICE AND |
| | ELECTRICAL PANELS ON PLAN. WPB FBC 107.2.1 |
| | 7. RISER DIAGRAM SHOWS AN EQUIPMENT GROUNDING CONDUCTOR |
| | (EGC) FROM THE METER CAN TO THE MAIN DISCONNECT. THIS |
| | CONDUIT SHOULD NOT INCLUDE AN EGC. PROVIDE CORRECTION. |
| | NEC 250.6; FBC RE E3610.4 |
| | 8. RISER DIAGRAM SHOWS (2) 250 KCMIL CONUCTORS FROM |
| | METER TO MAIN DISCONNECT, AND FROM MAIN DISCONNECT TO |
| | INTERIOR PANEL. A GROUNDED (NEUTRAL) CONDUCTOR IS |
| | REQUIRED AT EACH SERVICE DISCONNECT AND WHERE THER ARE |
| | 120 VOLT LOADS. PROVIDE CORRECTION. NEC 250.24(C); FBC |
| | RE E3607 |
| | 9. SMOKE ALARMS MUST BE INSTALLED AT LEAST 3 FEET FROM |
| | BATHROOM DOOR, 3 FEET FROM CEILING FANS, AND 3 FEET |
| | FROM ANY MECHANICAL DUCT. PROVIDE CORRECTIONS. FBC RE |
| | R314.3(4), NFPA 72:29.8.3.4 |
| | 10. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 |
| | 11. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE |
| | PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH |
| | CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE |
| | CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |