| 2019-09-16 08:20:14 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19080419 |
| | REVIEWED: SEPTEMBER 16, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | 1) PROVISOS: |
| | DEFERRED SUBMITTALS- |
| | INTERIOR STAIRWAY, RAILS AND GUARDS |
| | EXTERIOR STAIRWAY RAILS AND GUARDS |
| | SEPARATE PERMITS REQUIRED FOR-LANDSCAPE, FENCES |
| | CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM |
| | SAT-SUN |
| | - NO RESPONSE REQUIRED. PROVISOS WILL BE ADDED TO THE |
| | PLANS AT FINAL STAMPING. |
| | |
| | 2) 109.3 FBC[AMENDED] PROVIDE COPY OF PROPOSAL WITH |
| | CONTRACTOR TO SHOW WORK VALUE EQUAL TO THE AMOUNT SHOWN |
| | ON PERMIT APPLICATION, OR ADJUST VALUE TO MATCH ACTUAL |
| | COST OF WORK. PLEASE ADJUST FEE AT FRONT DESK. |
| | |
| | 3) 501.1.1 FBC[RE] ADDITIONS, ALTERATIONS, OR REPAIRS: |
| | GENERAL. ADDITIONS, ALTERATIONS, OR REPAIRS TO AN |
| | EXISTING BUILDING, BUILDING SYSTEM OR PORTION THEREOF |
| | SHALL COMPLY WITH SECTION R502, R503 OR R504. UNALTERED |
| | PORTIONS OF THE EXISTING BUILDING OR BUILDING SUPPLY |
| | SYSTEM SHALL NOT BE REQUIRED TO COMPLY WITH THIS CODE. |
| | - PLEASE PROVIDE DOCUMENTATION TO SUPPORT THE METHOD |
| | CHOSEN FOR COMPLIANCE. |
| | |
| | 4) 408.1 FBC[R] PROVIDE VENTING CALCULATIONS FOR UNDER |
| | FLOOR SPACE, OR FOLLOW REQUIREMENTS FOR UNVENTED. |
| | - IF ADDITION CRAWL SPACE COMMUNICATES WITH EXISTING |
| | PLEASE INCLUDE EXISTING IN CALCULATION. |
| | |
| | 5) 408.4 FBC[R] PROVIDE ACCESS TO THE UNDER FLOOR SPACE |
| | 18X24 MINIMUM. |
| | - SHOW EXISTING ACCESS, OR PROVIDE ACCESS POINT TO |
| | FLOOR CRAWL SPACE IF APPLICABLE. |
| | |
| | 6) 806 FBC[R] SUPPLY VENTING CALCULATIONS FOR THE ATTIC |
| | AND HOW THE AREA OF VENTING WILL BE ACHIEVED, OR FOLLOW |
| | R806.5 FOR UNVENTED. |
| | - PLEASE PROVIDE PRODUCT APPROVAL FOR ROOF INSULATION |
| | AND ATTACHMENT ACCORDING TO GENERAL LIMITATIONS 7 ON |
| | NOA 15-0729.18 |
| | |
| | 7) 806.5 FBC[R] UNVENTED ATTIC AND UNVENTED ENCLOSED |
| | RAFTER ASSEMBLIES. 5.1.2. WHERE AIR-PERMEABLE |
| | INSULATION IS PROVIDED INSIDE THE BUILDING THERMAL |
| | ENVELOPE, IT SHALL BE INSTALLED IN ACCORDANCE WITH |
| | SECTION 5.1.1. IN ADDITION TO THE AIR-PERMEABLE |
| | INSULATION INSTALLED DIRECTLY BELOW THE STRUCTURAL |
| | SHEATHING, RIGID BOARD OR SHEET INSULATION SHALL BE |
| | INSTALLED DIRECTLY ABOVE THE STRUCTURAL ROOF SHEATHING |
| | IN ACCORDANCE WITH THE R-VALUES IN TABLE R806.5 FOR |
| | CONDENSATION CONTROL. |
| | - PLEASE REVIEW THIS SECTION FOR AIR PERMEABLE |
| | INSULATION AT ROOF DECK. |
| | |
| | 8) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR |
| | WINDOW MULL AND GARAGE DOORS, OR INDICATE THAT YOU |
| | WOULD LIKE THEM DEFERRED. |
| | - |
| | |
| | 9) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT ATTACHMENT |
| | FOR ROOF INSULATION, OR INDICATE THAT YOU WOULD LIKE IT |
| | DEFERRED. |
| | - ALSO, PROVIDE ENHANCED NAILING ENGINEERED FOR |
| | EXPOSURE C IN THE 3 WIND ZONES ESTABLISHED ON SHEET |
| | A-2C. PLEASE PROVIDE PRODUCT APPROVAL FOR ROOF |
| | INSULATION AND ATTACHMENT ACCORDING TO GENERAL |
| | LIMITATIONS 7 ON NOA 15-0729.18 |
| | |
| | 10) 107.2.1.2 FBC[AMENDED] SUBMIT TWO SETS OF SHOP |
| | DRAWINGS FOR STAIRCASE, APPROVED BY DESIGNER OF RECORD, |
| | FOR REVIEW BY WPB BUILDING DEPARTMENT AS A SUBMITTAL. |
| | |
| | NOTES: |
| | |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |