| 2019-09-09 13:49:35 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE APPEARS TO BE CONFUSION IF THIS IS AN EXISTING |
| | GENERATOR REPLACEMENT OR NEW. |
| | |
| | PLEASE CLARIFY. |
| | |
| | COMPLIED WITH WRITTEN "NEW" ON PLAN. |
| | |
| | |
| | |
| | 2) THERE ARE NO INDICATIONS OF COMPLIANCE WITH ANY NFPA |
| | CODES. |
| | |
| | THE INSTALLATION SHALL COMPLY WITH NFPA 37, 54 AND IF |
| | APPLICABLE 110 IF PROVIDEING FOR A LIFE SAFETY SYSTEM, |
| | FIRE ALARM AND/OR FIRE SPRINKLER. |
| | |
| | NOT COMPLIED |
| | |
| | PLEASE PROVIDE A NOTE OF COMPLIANCE WITH THE NOTED |
| | CODES. |
| | |
| | |
| | |
| | 3) PLEASE PROVIDE DIMENSIONS AND LOCATIONS TO THE |
| | NEAREST BUILDING AND OF ALL DOORS, WINDOWS, AND OPEN |
| | CANOPIES THAT CAN ALLOW FOR ACCUMULATION OF EXHAUST |
| | FUMES. |
| | |
| | NOT COMPLIED |
| | |
| | THE ACCUMULATION OF EXHAUST FUMES CAN BE TRAPPED UNDER |
| | CANOPYS AND SEEP THRU OVERHANGS, WINDOWS AND DOORS. |
| | |
| | PER NFPA 37 |
| | |
| | 8.2.3 EXHAUST SYSTEM TERMINATION. |
| | 8.2.3.1* EXHAUST SYSTEMS SHALL TERMINATE OUTSIDE THE |
| | STRUCTURE |
| | AT A POINT WHERE HOT GASES, SPARKS, OR PRODUCTS OF |
| | COMBUSTION |
| | WILL DISCHARGE TO A SAFE LOCATION. |
| | 8.2.3.2 EXHAUST SYSTEM TERMINATIONS SHALL NOT BE |
| | DIRECTED TOWARD |
| | COMBUSTIBLE MATERIAL OR STRUCTURES OR INTO ATMOSPHERES |
| | CONTAINING FLAMMABLE GASES, FLAMMABLE VAPORS, OR |
| | COMBUSTIBLE |
| | DUSTS. |
| | |
| | PLEASE PROVIDE A ALL APPLICABLE DIMENSIONS. |
| | |
| | |
| | |
| | 4) THERE IS NO CLEAR INDICATION OF EITHER POWERED BY LP |
| | OR NG AND THE LOCATIONS OF ANY PROPOSED TANKS OR |
| | PIPING. |
| | |
| | NOT COMPLIED |
| | |
| | IT APPEARS TO BE NG..... |
| | |
| | PLEASE CLARIFY AND PROVIDE APPLICABLE DETAILS. |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |