2019-08-14 14:39:0408/14/2019 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1) CITY RECORDS SHOW AN EXISTING SYSTEM BUT THERE ARE
 NO PERMIT OR INSPECTIONS ON FILE FOR THIS SYSTEM. THE
 BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO
 THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. 2017 FBC RES. SECS.
 G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 2) REGULATOR REQUIRED AT GENERATOR AND MANUFACTURER?S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC FG
 SEC. 410.1 OR 2017 FBC RES. SEC. G2421.1.
  
 3) SHOW THE BTU LOAD FOR ALL APPLIANCES ON ISOMETRIC.
 LABEL SHUTOFF VALUE ON EXISTING KITCHEN PER THE 2017
 FBC FG SEC. 402.2.
  
 4) THE ADDRESS OF THE PROJECT MUST BE ON PLAN ON SP1
 AND ISOMETRIC PER WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5) SHOW UNION ON THE ISOMETRIC DRAWING PER 2017 FBC FG
 410.2.
  
 6) A SEPARATE PERMIT IS REACQUIRED FOR GAS PER WPB
 AMENDMENTS TO THE FBC SEC. 105.1.
  
 7) SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE
 DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM PER THE 2017 FBC FG SEC. 402.3 OR 2017 FBC RES.
 SEC. G2413.3
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  