| 2019-08-14 14:39:04 | 08/14/2019 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1) CITY RECORDS SHOW AN EXISTING SYSTEM BUT THERE ARE |
| | NO PERMIT OR INSPECTIONS ON FILE FOR THIS SYSTEM. THE |
| | BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO |
| | THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING |
| | SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING |
| | SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING |
| | SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS |
| | THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH |
| | APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH |
| | APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF |
| | PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| | OUTLET AND THE LOAD OF THE SECTION. 2017 FBC RES. SECS. |
| | G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. |
| | |
| | 2) REGULATOR REQUIRED AT GENERATOR AND MANUFACTURER?S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC FG |
| | SEC. 410.1 OR 2017 FBC RES. SEC. G2421.1. |
| | |
| | 3) SHOW THE BTU LOAD FOR ALL APPLIANCES ON ISOMETRIC. |
| | LABEL SHUTOFF VALUE ON EXISTING KITCHEN PER THE 2017 |
| | FBC FG SEC. 402.2. |
| | |
| | 4) THE ADDRESS OF THE PROJECT MUST BE ON PLAN ON SP1 |
| | AND ISOMETRIC PER WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 5) SHOW UNION ON THE ISOMETRIC DRAWING PER 2017 FBC FG |
| | 410.2. |
| | |
| | 6) A SEPARATE PERMIT IS REACQUIRED FOR GAS PER WPB |
| | AMENDMENTS TO THE FBC SEC. 105.1. |
| | |
| | 7) SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE |
| | DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| | OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR |
| | ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| | SYSTEM PER THE 2017 FBC FG SEC. 402.3 OR 2017 FBC RES. |
| | SEC. G2413.3 |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |