2019-08-20 14:07:45THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE APPEARS TO BE CONFUSION IF THIS IS AN EXISTING
 GENERATOR REPLACEMENT OR NEW.
  
 PLEASE CLARIFY.
  
  
  
 2) THERE ARE NO INDICATIONS OF COMPLIANCE WITH ANY NFPA
 CODES.
  
 THE INSTALLATION SHALL COMPLY WITH NFPA 37, 54 AND IF
 APPLICABLE 110 IF PROVIDEING FOR A LIFE SAFETY SYSTEM,
 FIRE ALARM AND/OR FIRE SPRINKLER.
  
  
  
 3) PLEASE PROVIDE DIMENSIONS AND LOCATIONS TO THE
 NEAREST BUILDING AND OF ALL DOORS, WINDOWS, AND OPEN
 CANOPIES THAT CAN ALLOW FOR ACCUMULATION OF EXHAUST
 FUMES.
  
  
  
 4) THERE IS NO CLEAR INDICATION OF EITHER POWERED BY LP
 OR NG AND THE LOCATIONS OF ANY PROPOSED TANKS OR
 PIPING.
  
 PLEASE CLARIFY AND PROVIDE APPLICABLE DETAILS.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  