| 2019-08-20 14:07:45 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE APPEARS TO BE CONFUSION IF THIS IS AN EXISTING | | | GENERATOR REPLACEMENT OR NEW. | | | | | | PLEASE CLARIFY. | | | | | | | | | | | | 2) THERE ARE NO INDICATIONS OF COMPLIANCE WITH ANY NFPA | | | CODES. | | | | | | THE INSTALLATION SHALL COMPLY WITH NFPA 37, 54 AND IF | | | APPLICABLE 110 IF PROVIDEING FOR A LIFE SAFETY SYSTEM, | | | FIRE ALARM AND/OR FIRE SPRINKLER. | | | | | | | | | | | | 3) PLEASE PROVIDE DIMENSIONS AND LOCATIONS TO THE | | | NEAREST BUILDING AND OF ALL DOORS, WINDOWS, AND OPEN | | | CANOPIES THAT CAN ALLOW FOR ACCUMULATION OF EXHAUST | | | FUMES. | | | | | | | | | | | | 4) THERE IS NO CLEAR INDICATION OF EITHER POWERED BY LP | | | OR NG AND THE LOCATIONS OF ANY PROPOSED TANKS OR | | | PIPING. | | | | | | PLEASE CLARIFY AND PROVIDE APPLICABLE DETAILS. | | | | | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|