Plan Review Notes
Plan Review Notes For Permit 19080405
Permit Number 19080405
Review Stop P
Sequence Number 1
Notes
Date Text
2019-08-22 11:10:57CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMEMTS: DENIED
 1.PER WPB FBC 107.2.1, PROVIDE ON THE DEMO PLAN,
 ORIGINAL CONFIGURATIONS OF FIXTURES AND APPLIANCES IN
 THE KITCHEN AND IN THE BATHROOMS BEING REMODELED.
 2.RE: P-1 SANITARY RISER DIAGRAM AND PLAN VIEW PIPING,
 SEE THE FOLLOWING AND CORRECT.
 3. WITH THE EXCEPTION OF THE VENT FOR THE WASHER, ALL
 OF THE VENTS TO THE EXTERIOR SHOWN ON THE SANITARY
 PIPING DIAGRAMS (RISER AND PLAN VIEW) DO NOT COMPLY
 WITH THE REQUIREMENTS OF FBC RES P3104.3 (VENT
 CONNECTION TO DRAINAGE SYSTEM. A DRY VENT CONNECTING TO
 A HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTERLINE
 OF THE HORIZONTAL DRAIN PIPE.) AND FBC RES P3104.4
 (VERTICAL RISE OF VENT. A DRY VENT SHALL RISE
 VERTICALLY TO NOT LESS THAN 6 INCHES ABOVE THE FLOOD
 LEVEL RIM OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING
 VENTED.)
 4. PER FBC RES 3108.1, THE BATHTUB SHALL NOT BE VENTED
 BY THE WASHER. THE BATHTUB FIXTURE DRAIN SHALL CONNECT
 TO THE HORIZONTAL WET VENT OR BE INDIVIDUALLY VENTED IN
 ACCORDANCE WITH FBC RES 3105 AND P3601.1.
 5. PER FBC RES P3108.1, THE SHOWER DRAIN IN BATHROOM #1
 SHALL NOT CONNECT TO THE WATER CLOSET DRAIN AHEAD OF
 THE VENT. EACH FIXTURE DRAIN SHALL CONNECT
 INDEPENDENTLY TO THE WET VENT OR SHALL HAVE A DRY VENT
 CONFORMING TO FBC RES P3104.3 AND P3104.4.
 6. PER FBC RES 3105.2 AND P3201.5(3), PROVIDE VENT AT
 THE POINT WHERE THE TRAPPED FIXTURE DRAIN GOES FROM
 HORIZONTAL TO VERTICAL (SEE ALL VANITIES AND SINKS).
 7. GENERAL NOTE: PLEASE REFER TO FBC RES SECTION 3108
 WET VENTING WHEN DESIGNING THE BATHROOM DRAINAGE, WASTE
 AND VENTS. ADDITIONALLY, THE USE OF AIR ADMITTANCE
 VALVES IN LIEU OF VENTS TO THE EXTERIOR IS PERMITTED
 (SEE FBC RES P3104.1, EXCEPTION) AS LONG AS A MINIMUM
 OF ONE (1) VENT PER BUILDING DRAIN(YOU HAVE TWO (2)
 BUILDING DRAINS) EXTENDS TO THE EXTERIOR (SEE FBC RES
 P3102.1).
 8. AS THE PLANS ARE NOT SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER OR ARCHITECT, THE PLUMBING PLAN
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE
 DESIGNER PER WPB FBC 107.2.1.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 AS THE PLANS ARE NOT SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER OR ARCHITECT, THE PLUMBING PLAN
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE
 DESIGNER PER WPB FBC 107.2.1.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19080405 140 MONROE DR
  