| 2019-08-29 15:37:04 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | NFPA 99 = HEALTH CARE FACILITIES CODE |
| | NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | |
| | PLUMBING COMMEMTS: DENIED |
| | |
| | 1 AS THE PLANS ARE NOT SIGNED AND SEALED BY A |
| | PROFESSIONAL ENGINEER OR ARCHITECT, THE PLUMBING PLAN |
| | SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE |
| | DESIGNER PER WPB FBC 107.2.1. |
| | |
| | 2. RE: PLAN SHEET P-1; SANITARY RISER DIAGRAM. IF THE |
| | EXISTING WASHER IS CONNECTED TO A TWO STACK WITH REVENT |
| | SYSTEM THEN (1) NEW WASHER DRAIN SHALL CONNECT TO |
| | EXISTING WASTE STACK, NOT TO THE VENT AND (2) A VENT |
| | SHALL BE PROVIDED AT THE POINT THAT THE TRAPPED WASHER |
| | DRAIN CHANGES FROM HORIZONTAL TO VERTICAL AND SHALL |
| | CONNECT TO THE EXISTING VENT STACK (FBC PL 905.1). IF |
| | THE EXISTING WASHER CONNECTS TO A SINGLE PIPE WASTE |
| | STACK VENT FBC PL 913), THEN A VENT SHALL BE PROVIDED |
| | AT THE POINT THAT THE TRAPPED CLOTHES WASHER DRAIN |
| | CHANGES FROM HORIZONTAL TO VERTICAL AND SHALL CONNECT |
| | TO AN EXISTING BRANCH VENT OR VENT STACK (FBC PL |
| | 905.1). IF AN EXISTING BRANCH VENT OR VENT STACK IS NOT |
| | AVAILABLE, THE NEW HORIZONTAL DRAIN SHALL BE SIZED 3? |
| | (AS REQUIRED BY MANUFACTURER OF AIR ADMITTANCE VALVE |
| | INSTALLATION GUIDE) TO THE POINT OF HORIZONTAL TO |
| | VERTICAL THEN CAN BE 2? SIZE. AN AIR ADMITTANCE VALVE |
| | SHALL BE INSTALLED ABOVE THE POINT THAT THE TRAPPED |
| | CLOTHES WASHER DRAIN CHANGES FROM HORIZONTAL TO |
| | VERTICAL. PER WPB FBC 107.2.1, CONFIRM WHICH TYPE OF |
| | WASTE AND VENT SYSTEM IS INVOLVED, THE SIZES OF THE |
| | EXISTING AND SHOW ON THE SANITARY RISER DIAGRAM. |
| | SPECIFY THE TYPE OF MATERIAL USED FOR NEW AND EXISTING |
| | PIPING, I.E. PVC DWV, CAST IRON, ETC. |
| | |
| | 3. RE: PLAN SHEET P-1; SHOWER DETAIL. PROVIDE ON THE |
| | ELEVATION CUT THROUGH DETAIL OF THE SHOWER COMPARTMENT |
| | (FBC PL 417.5 THROUGH 417.5.2.6) THE TYPE OF LINER, THE |
| | HEIGHT ABOVE THE CURB IT EXTENDS, EXISTING SLAB |
| | THICKNESS AND THE TYPE OF MATERIAL USED FOR NEW AND |
| | EXISTING PIPING, I.E. PVC DWV, CAST IRON, ETC. |
| | |
| | 4. PROVIDE UL FIRE SAFING DETAIL(S) FOR THROUGH THE |
| | FLOOR PIPE PENETRATIONS. COMPLY WITH THE REQUIREMENTS |
| | OF FBC CHAPTER 7. |
| | |
| | 5. PROVIDE ANTI-SCALD VALVES IN ALL SHOWERS PER FBC PL |
| | 424.3. |
| | |
| | 6. PROVIDE WATER HAMMER ARRESTORS CONFORMING TO ASSA |
| | 1010 AT DISHWASHER, REFRIGERATOR ICE LINE AND CLOTHES |
| | WASHER PER FBC PL 604.9 |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19080396 2425 PRESIDENTIAL WAY 403 |
| | |