| Plan Review Notes For Permit 19080377 |
| Permit Number |
19080377 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-08-21 10:23:59 | PERMIT #19080377 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | | | | BRITTANY WOODS | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4754 | | | | | | | | | 1.) PERMIT 19020767 - THERE ARE NO INSPECTION COMPLETED | | | FOR FIRE UNDER THE MASTER PERMIT | | | 2.) NEED TO PROVIDE SEQUENCE OF OPERATION IN EITHER AN | | | INPUT/OUTPUT MATRIX | | | OR NARRATIVE FORM | | | 3.) DETAILS OF CEILING GEOMETRIES, INCLUDING BEAMS AND | | | SOLID | | | JOISTS, WHERE AUTOMATIC FIRE DETECTION IS BEING | | | PROPOSED | | | 4.) PROVIDE OWNER?S MANUAL AND MANUFACTURER?S PUBLISHED | | | INSTRUCTIONS | | | COVERING ALL SYSTEM EQUIPMENT | | | 5.) NEED CLARIFICATION ON THE REASON FOR THE | | | MODIFICATION MADE TO REMOVE SMOKE RELEASE DOOR HOLDERS | | | AND THE ASSOCIATED SMOKE DETECTOR AND CONTROL RELAY. |
|