| Plan Review Notes For Permit 19080336 |
| Permit Number |
19080336 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-08-13 09:48:19 | FIRE COMMENTS ADDRESSED BY CONTRACTOR EMAIL AND FILENET | | | VERIFICATIONS. | | | PML | | 2019-08-07 15:38:47 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THE IS NO INDICATION WITHIN THE ROOM, WHERE A | | | CEILING CHANGE IS INDICTED, THAT THE FIRE SPRINKLER | | | ORIENTATION HAS CHANGED. | | | | | | IF THESE ARE NOW UPRIGHTS, THOSE HEADS SHOULD BE | | | INDICATED AS SUCH IN A CLOUDED REVISION. | | | | | | | | | | | | 2) THE IS NO CHANGE IN THE COUNT WITHIN THE SPRINKLER | | | HEAD LEGEND. | | | | | | IF THERE ARE NEW UPRIGHTS AND REDUCE PENDENTS, THATOSE | | | CHANGES SHOULD REFLECT IN THE LEGEND IN A CLOULDED | | | REVISION. | | | | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|