2019-08-13 09:48:19FIRE COMMENTS ADDRESSED BY CONTRACTOR EMAIL AND FILENET
 VERIFICATIONS.
 PML
2019-08-07 15:38:47THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE IS NO INDICATION WITHIN THE ROOM, WHERE A
 CEILING CHANGE IS INDICTED, THAT THE FIRE SPRINKLER
 ORIENTATION HAS CHANGED.
  
 IF THESE ARE NOW UPRIGHTS, THOSE HEADS SHOULD BE
 INDICATED AS SUCH IN A CLOUDED REVISION.
  
  
  
 2) THE IS NO CHANGE IN THE COUNT WITHIN THE SPRINKLER
 HEAD LEGEND.
  
 IF THERE ARE NEW UPRIGHTS AND REDUCE PENDENTS, THATOSE
 CHANGES SHOULD REFLECT IN THE LEGEND IN A CLOULDED
 REVISION.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  