| 2019-09-26 13:09:23 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | NFPA 99 = HEALTH CARE FACILITIES CODE |
| | NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 2ND REVIEW |
| | |
| | PLUMBING COMMEMTS: DENIED |
| | 1. SECOND REQUEST; IT IS NOTED THAT THE ARCHITECT HAS |
| | DELETED THE S-2 SINK AND ASSOCIATED MILL WORK. HOWEVER, |
| | AS PER WPB FBC 107.2.1, THE ELEVATION DETAIL OF |
| | MILLWORK FOR PLUMBING FIXTURE S-1 INDICATING MAXIMUM 2 |
| | FEET-10 INCHES TO THE TOP OF THE CABINET OR THE FIXTURE |
| | RIM, WHICHEVER IS HIGHER IS STILL REQUIRED, AS WELL AS |
| | DIMENSIONED CLEAR FLOOR SPACE FOR THE SINK. COMPLY WITH |
| | FBC ACC SECTIONS 212, 804, 305 AND 606. REVISE TO |
| | COMPLY. |
| | 2. PLAN SHEET A-1 NO LONGER SHOWS THE SINK OR MILLWORK |
| | FOR SINK S-2. PLAN SHEET P-2 INDICATES PLUMBING AND |
| | FIXTURE FOR S-2. PLEASE CLARIFY |
| | 3. PLAN SHEET P-1 IS NOT INCLUDED IN THE SUBMITTAL AND |
| | IS REQUIRED PER WPB FBC 107.2.1. |
| | 4. REGARDING SPECIFICATION FOR THE OWNER SUPPLIED |
| | SHAMPOO BOWL, PLEASE SEE THE ADDITIONAL DOCUMENTATION |
| | PROVIDED BY THE MANUFACTURER AND ATTACHED TO THE |
| | OVERVIEW SHEET OF THE AVERY BACKWASH SHAMPOO SYSTEM. |
| | THIS DOCUMENTATION IS CERTIFICATION THAT THE BACKFLOW |
| | PREVENTER COMPLIES WITH THE REQUIREMENTS OF FBC PL |
| | 608.2 BUT IS INVALID AFTER SEPTEMBER OF 2019. PER WPB |
| | FBC 107.2.1, PROVIDE A NEW CERTIFICATE SHOWING |
| | COMPLIANCE AT THE TIME OF PERMIT ISSUANCE. CALL MINERVA |
| | BEAUTY 888-332-0123 TECHNICAL SUPPORT FOR UPDATED |
| | CERTIFICATE. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19080334 416 CLEMATIS ST |
| | |
| | |