2019-09-27 14:16:34SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
  
 ORIGINAL COMMENT:
 1) THE COVERSHEET LIST THE PROJECT DATA. THE PLAN
 INDICATES THIS NEW TENANT SPACE IS TO BE A BUSINESS
 OCCUPANCY. CURRENTLY THE SPACE IS A DRUG STORE WHICH IS
 A MERCANTILE OCCUPANCY. PLEASE SEE CHAPTER 10 OF THE
 EXISTING BUILDING CODE SECTION 1001.2.2.1 FOR PARTIAL
 CHANGE OF OCCUPANCY REQUIREMENTS. WHERE A PORTION OF A
 BUILDING IS CHANGING OCCUPANCIES SECTION 1012 OF THE
 EXISTING BUILDING CODE SHALL APPLY.
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 RESPONSE:
 A) THE PROJECT DATA INFORMATION ON THE COVERSHEET IS
 NOT CLEAR. CURRENTLY THE SPACE IS A DRUG STORE WHICH IS
 MERCANTILE OCCUPANCY. IT LOOKS LIKE A PORTION OF THE
 DRUG STORE IS PROPOSED TO BE A BEAUTY SALON WHICH IS
 BUSINESS OCCUPANCY. ACCORDING TO FIRST FLOOR PLAN ON
 SHEET A-1 THE PHARMACY WILL REMAIN ON THE OTHER PART OF
 THE BUILDING. THEREFORE, THE DRUG STORE MERCANTILE
 OCCUPANCY STILL REMAINS. THIS IS A PARTIAL CHANGE OF
 OCCUPANCY CLASSIFICATION WITHOUT SEPARATION. PROJECT
 DATA SHALL BE CLEAR IN STATING THE EXISTING OCCUPANCY
 GROUP AND THE PROPOSED PARTIAL OCCUPANCY GROUP. SINCE
 THERE IS NOT SEPARATION AMONG THE OCCUPANCY
 CLASSIFICATIONS, THEN THE MOST RESTRICTIVE OCCUPANCY
 WILL PREVAIL FOR ENTIRE BUILDING. SECTION 1012.1.1.1
 FBC-EXISTING BUILDING.
  
 B) PROPOSED FLOOR PLAN DOESN'T SHOW THE LAYOUT OF THE
 PHARMACY AREA TO REMAIN. PROVIDE PLANS SHOWING THE
 AREAS THAT ARE GOING TO BE OCCUPIED BY THE PHARMACY.
 SHOW ALL THE ISLES, ETC. SEC. 107.2.1 CITY AMENDMENTS.
 SEC. 1012.4.2 FBC-EXISTING BUILDING. SEC. 1018
 FBC-BUILDING.
  
 C) THERE IS NO DIMENSION FOR THE CORRIDOR (HALL 108).
 PROVIDE DIMENSION. SEC. 1012.4.2 FBC-EXISTING BUILDING.
 SEC. 1020.2 FBC-BUILDING.
  
  
 2) OK
  
 3A) OK
  
 ORIGINAL COMMENT:
 3B) SHEET A1 DETAIL 1 SHOWS THE TENANT WALLS EXTENDING
 UP HALFWAY TO THE CEILING. ABOVE THIS AREA THE AIR
 COMMUNICATES WITH THE EXIT CORRIDOR AND OTHER TENANT
 SPACES. IN THE 2017 FBC-B SECTION 2801.1. MECHANICAL
 APPLIANCES, EQUIPMENT AND SYSTEMS SHALL BE CONSTRUCTED,
 INSTALLED AND MAINTAINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, MECHANICAL. IN THE MECHANICAL CODE UNDER
 VENTILATION TABLE 403.3.1.1 SPECIALTY SHOPS PLEASE SEE
 BEAUTY SALON REQUIREMENTS (SEE FOOTNOTE B) FOR
 VENTILATION AND IF MANICURES AND OR PEDICURE STATIONS
 SOURCE CAPTURE SYSTEMS ARE REQUIRED AT EACH STATION,
 SEE FOOTNOTES B & H. FOOTNOTE B STATES MECHANICAL
 EXHAUST REQUIRED AND THE RECIRCULATION OF AIR FROM SUCH
 SPACES IS PROHIBITED. RECIRCULATION OF AIR THAT IS
 CONTAINED COMPLETELY WITHIN SUCH SPACES SHALL NOT BE
 PROHIBITED (SEE SECTION 403.2.1, ITEM 3).
  
 RESPONSE:
 THIS ITEMS NEEDS TO BE COORDINATED WITH THE MECHANICAL
 PLANS EXAMINER AND THE ENGINEER OF RECORD. (MECHANICAL
 PLANS EXAMINER FOR THIS JOB IS OUT OF THE OFFICE TODAY.
 I WILL TALK TO HIM WHEN HE IS BACK). IT IS NOT CLEAR IF
 MECHAICAL PLAN REVIEWER AND THE ENGINEER OF RECORD ARE
 AWARE OF THE FACT THAT THE TENANT SEPARATION WALLS
 DON'T GO ALL THE WAY UP TO THE CEILING. (SEC. 1009.1
 FBC-EXISTING BUILDING). ALSO, THE EXHAUST LOCATION
 NEEDS TO BE REVIEWED. ACCORDING TO SEC. 502.1.1
 FBC-MECHANICAL, THE INLET TO AN EXHAUST SYSTEM SHALL BE
 LOCATED IN THE AREA OF HEAVIEST CONCENTRATION OF
 CONTAMINANTS. HEAVIEST CONCENTRATION MAY BE BY THE
 STYLING AREA.
  
  
 3C) OK
  
 3D) OK
  
 3E) OK
  
 ORIGINAL COMMENT:
 3F) SHEET A-2 SHOWS 3 DETAILS, 3, 4 & 5. DETAIL 5 SHOWS
 THE USE OF (2) 2X6 BUCKS BEING FASTENED TO STEEL BEAM
 AND COLUMNS WITH 2 INCH SCREWS AT 12 INCHES ON CENTER.
 3F)(2) DETAILS 3 AND 4 DO NOT SHOW THE INSTALLATION OF
 A DOUBLE BUCK ATTACHED TO THE STEEL BEAM OR COLUMN.
 107.2.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 RESPONSE:
 DETAIL IS NOT CLEAR. DETAIL 5 SHOWS DOUBLE 2X4 BUCKS.
 SIZE OF SCREW SPECIFIED DOESN'T SEEM TO BE LONG ENOUGH
 TO FASTEN THE TWO BUCKS TO THE STEEL COLUMN/BEAM. IN
 ADDITION, THE TWO 2X4 BUCKS ARE THE STRUCTURAL BUCKS
 TRANSFERRING THE NEW DOORS AND STOREFRONT WIND LOADS TO
 THE STEEL COLUMN/BEAM. PROVIDE CALCULATIONS SHOWING
 THAT THE PROPOSED CONNECTION DETAIL WILL SUPPORT ALL
 THE LOADS. SEC. 107.2.1.2 CITY AMENDMENTS. SEC. 1609.1
 FBC-BUILDING.
  
 4) OK. THIS WILL BE PROVIDED AT TIME OF INSPECTION.
  
 SHEET A-2 SHOWS THE USE OF WELDED AND BOLTED
 CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD
 PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS
 FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
  
 DEFERRED SUBMITTAL:
 5) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS
  
 DEFERRED SUBMITTAL:
 6) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 7) OK.
  
 8) ASBESTOS:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ASBESTOS IN THE SUBJECT LINE.
  
 SEC. 469.003 FLORIDA STATUTES.
  
  
 9) PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE.
 CALL (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT
 ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC
 TFEES/FORMS/QUESTIONNAIRE.PDF
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 NOTE:
 SEPARATE FIRE SPRINKLER PERMIT IS REQUIRED SHOWING THE
 PROPOSED ALTERATIONS TO THIS BUILDING.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  