| 2019-09-27 14:16:34 | SECOND BUILDING REVIEW CHECKLIST. |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 1) THE COVERSHEET LIST THE PROJECT DATA. THE PLAN |
| | INDICATES THIS NEW TENANT SPACE IS TO BE A BUSINESS |
| | OCCUPANCY. CURRENTLY THE SPACE IS A DRUG STORE WHICH IS |
| | A MERCANTILE OCCUPANCY. PLEASE SEE CHAPTER 10 OF THE |
| | EXISTING BUILDING CODE SECTION 1001.2.2.1 FOR PARTIAL |
| | CHANGE OF OCCUPANCY REQUIREMENTS. WHERE A PORTION OF A |
| | BUILDING IS CHANGING OCCUPANCIES SECTION 1012 OF THE |
| | EXISTING BUILDING CODE SHALL APPLY. |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | RESPONSE: |
| | A) THE PROJECT DATA INFORMATION ON THE COVERSHEET IS |
| | NOT CLEAR. CURRENTLY THE SPACE IS A DRUG STORE WHICH IS |
| | MERCANTILE OCCUPANCY. IT LOOKS LIKE A PORTION OF THE |
| | DRUG STORE IS PROPOSED TO BE A BEAUTY SALON WHICH IS |
| | BUSINESS OCCUPANCY. ACCORDING TO FIRST FLOOR PLAN ON |
| | SHEET A-1 THE PHARMACY WILL REMAIN ON THE OTHER PART OF |
| | THE BUILDING. THEREFORE, THE DRUG STORE MERCANTILE |
| | OCCUPANCY STILL REMAINS. THIS IS A PARTIAL CHANGE OF |
| | OCCUPANCY CLASSIFICATION WITHOUT SEPARATION. PROJECT |
| | DATA SHALL BE CLEAR IN STATING THE EXISTING OCCUPANCY |
| | GROUP AND THE PROPOSED PARTIAL OCCUPANCY GROUP. SINCE |
| | THERE IS NOT SEPARATION AMONG THE OCCUPANCY |
| | CLASSIFICATIONS, THEN THE MOST RESTRICTIVE OCCUPANCY |
| | WILL PREVAIL FOR ENTIRE BUILDING. SECTION 1012.1.1.1 |
| | FBC-EXISTING BUILDING. |
| | |
| | B) PROPOSED FLOOR PLAN DOESN'T SHOW THE LAYOUT OF THE |
| | PHARMACY AREA TO REMAIN. PROVIDE PLANS SHOWING THE |
| | AREAS THAT ARE GOING TO BE OCCUPIED BY THE PHARMACY. |
| | SHOW ALL THE ISLES, ETC. SEC. 107.2.1 CITY AMENDMENTS. |
| | SEC. 1012.4.2 FBC-EXISTING BUILDING. SEC. 1018 |
| | FBC-BUILDING. |
| | |
| | C) THERE IS NO DIMENSION FOR THE CORRIDOR (HALL 108). |
| | PROVIDE DIMENSION. SEC. 1012.4.2 FBC-EXISTING BUILDING. |
| | SEC. 1020.2 FBC-BUILDING. |
| | |
| | |
| | 2) OK |
| | |
| | 3A) OK |
| | |
| | ORIGINAL COMMENT: |
| | 3B) SHEET A1 DETAIL 1 SHOWS THE TENANT WALLS EXTENDING |
| | UP HALFWAY TO THE CEILING. ABOVE THIS AREA THE AIR |
| | COMMUNICATES WITH THE EXIT CORRIDOR AND OTHER TENANT |
| | SPACES. IN THE 2017 FBC-B SECTION 2801.1. MECHANICAL |
| | APPLIANCES, EQUIPMENT AND SYSTEMS SHALL BE CONSTRUCTED, |
| | INSTALLED AND MAINTAINED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, MECHANICAL. IN THE MECHANICAL CODE UNDER |
| | VENTILATION TABLE 403.3.1.1 SPECIALTY SHOPS PLEASE SEE |
| | BEAUTY SALON REQUIREMENTS (SEE FOOTNOTE B) FOR |
| | VENTILATION AND IF MANICURES AND OR PEDICURE STATIONS |
| | SOURCE CAPTURE SYSTEMS ARE REQUIRED AT EACH STATION, |
| | SEE FOOTNOTES B & H. FOOTNOTE B STATES MECHANICAL |
| | EXHAUST REQUIRED AND THE RECIRCULATION OF AIR FROM SUCH |
| | SPACES IS PROHIBITED. RECIRCULATION OF AIR THAT IS |
| | CONTAINED COMPLETELY WITHIN SUCH SPACES SHALL NOT BE |
| | PROHIBITED (SEE SECTION 403.2.1, ITEM 3). |
| | |
| | RESPONSE: |
| | THIS ITEMS NEEDS TO BE COORDINATED WITH THE MECHANICAL |
| | PLANS EXAMINER AND THE ENGINEER OF RECORD. (MECHANICAL |
| | PLANS EXAMINER FOR THIS JOB IS OUT OF THE OFFICE TODAY. |
| | I WILL TALK TO HIM WHEN HE IS BACK). IT IS NOT CLEAR IF |
| | MECHAICAL PLAN REVIEWER AND THE ENGINEER OF RECORD ARE |
| | AWARE OF THE FACT THAT THE TENANT SEPARATION WALLS |
| | DON'T GO ALL THE WAY UP TO THE CEILING. (SEC. 1009.1 |
| | FBC-EXISTING BUILDING). ALSO, THE EXHAUST LOCATION |
| | NEEDS TO BE REVIEWED. ACCORDING TO SEC. 502.1.1 |
| | FBC-MECHANICAL, THE INLET TO AN EXHAUST SYSTEM SHALL BE |
| | LOCATED IN THE AREA OF HEAVIEST CONCENTRATION OF |
| | CONTAMINANTS. HEAVIEST CONCENTRATION MAY BE BY THE |
| | STYLING AREA. |
| | |
| | |
| | 3C) OK |
| | |
| | 3D) OK |
| | |
| | 3E) OK |
| | |
| | ORIGINAL COMMENT: |
| | 3F) SHEET A-2 SHOWS 3 DETAILS, 3, 4 & 5. DETAIL 5 SHOWS |
| | THE USE OF (2) 2X6 BUCKS BEING FASTENED TO STEEL BEAM |
| | AND COLUMNS WITH 2 INCH SCREWS AT 12 INCHES ON CENTER. |
| | 3F)(2) DETAILS 3 AND 4 DO NOT SHOW THE INSTALLATION OF |
| | A DOUBLE BUCK ATTACHED TO THE STEEL BEAM OR COLUMN. |
| | 107.2.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | RESPONSE: |
| | DETAIL IS NOT CLEAR. DETAIL 5 SHOWS DOUBLE 2X4 BUCKS. |
| | SIZE OF SCREW SPECIFIED DOESN'T SEEM TO BE LONG ENOUGH |
| | TO FASTEN THE TWO BUCKS TO THE STEEL COLUMN/BEAM. IN |
| | ADDITION, THE TWO 2X4 BUCKS ARE THE STRUCTURAL BUCKS |
| | TRANSFERRING THE NEW DOORS AND STOREFRONT WIND LOADS TO |
| | THE STEEL COLUMN/BEAM. PROVIDE CALCULATIONS SHOWING |
| | THAT THE PROPOSED CONNECTION DETAIL WILL SUPPORT ALL |
| | THE LOADS. SEC. 107.2.1.2 CITY AMENDMENTS. SEC. 1609.1 |
| | FBC-BUILDING. |
| | |
| | 4) OK. THIS WILL BE PROVIDED AT TIME OF INSPECTION. |
| | |
| | SHEET A-2 SHOWS THE USE OF WELDED AND BOLTED |
| | CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD |
| | PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE |
| | AMERICAN WELDING SOCIETY. |
| | 2017 FBC-B 2204.1 WELDING |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS |
| | FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING |
| | INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU. |
| | |
| | |
| | DEFERRED SUBMITTAL: |
| | 5) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS |
| | |
| | DEFERRED SUBMITTAL: |
| | 6) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 |
| | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| | LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 7) OK. |
| | |
| | 8) ASBESTOS: |
| | PLEASE PROVIDE A SIGNED ACKNOWLEDGMENT FROM THE |
| | CONTRACTOR, ON LETTERHEAD, STATING THAT THE |
| | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM |
| | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH |
| | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE |
| | GIVEN TIMELY. |
| | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS |
| | CAN BE FOUND ON THEIR WEBSITE: |
| | |
| | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE |
| | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- |
| | RENOVATION.HTML |
| | |
| | THE CONTRACTOR ACKNOWLEDGMENT CAN BE SENT VIA EMAIL TO |
| | [email protected]. THE INFORMATION SHOULD BE IN PDF |
| | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE |
| | THE PERMIT NUMBER AND ASBESTOS IN THE SUBJECT LINE. |
| | |
| | SEC. 469.003 FLORIDA STATUTES. |
| | |
| | |
| | 9) PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. |
| | CALL (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT |
| | ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE |
| | RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS |
| | APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE |
| | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE |
| | FORM CAN BE FOUND AT: |
| | HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC |
| | TFEES/FORMS/QUESTIONNAIRE.PDF |
| | |
| | 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | NOTE: |
| | SEPARATE FIRE SPRINKLER PERMIT IS REQUIRED SHOWING THE |
| | PROPOSED ALTERATIONS TO THIS BUILDING. |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |