| Date |
Text |
| 2019-08-29 10:46:31 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | NFPA 99 = HEALTH CARE FACILITIES CODE |
| | NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | |
| | PLUMBING COMMEMTS: DENIED |
| | |
| | 1. RE: PLAN SHEET P-2, WATER ISOMETRIC NOTE #2; FBC |
| | 2318.1.15 AND 2517.5.1.1 DO NOT APPEAR TO ADDRESS |
| | ANYTHING CONCERNING WALL HUNG PLUMBING FIXTURES. PER |
| | WPB FBC 107.2.1, PLEASE CLARIFY. |
| | 2. PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR THE |
| | OWNER SUPPLIED SHAMPOO BOWL. SPECIFICATION SHALL |
| | INCLUDE PROVISION FOR BACKFLOW PREVENTION AS REQUIRED |
| | BY FBC PL SECTION 608. IF THERE IS NO PROVISION THEN |
| | THE ENGINEER SHALL PROVIDE FOR SAID PROTECTION AND |
| | SPECIFY TYPE ON THE PLANS. |
| | 3. PER WPB FBC 107.2.1, PROVIDE ELEVATION DETAIL OF |
| | MILLWORK FOR PLUMBING FIXTURES S-1 AND S-2 SHOWING |
| | MAXIMUM 2?-10? TO THE TOP OF THE CABINET OR THE FIXTURE |
| | RIM, WHICHEVER IS HIGHER. ADDITIONALLY, PROVIDE |
| | DIMENSIONED CLEAR FLOOR SPACES AND ANY REQUIRED TURNING |
| | RADIUS TO THE FIXTURES AND AFFECTED APPLIANCES. COMPLY |
| | WITH FBC ACC SECTIONS 212, 804, 305 AND 606. PLEASE |
| | NOTE THAT THE U-SHAPED CABINET CONFIGURATION DOES NOT |
| | COMPLY WITH THE REQUIREMENTS OF FBC ACC 804.2.2. REVISE |
| | TO COMPLY. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | |