Plan Review Notes
Plan Review Notes For Permit 19080334
Permit Number 19080334
Review Stop B
Sequence Number 1
Notes
Date Text
2019-08-26 07:00:202017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19080334
 ADD: 416 CLEMATIS ST.
 CONT: MONTIERRE DEVELOPMENT
 TEL: 407-562-6311
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 1ST REVIEW
 DATE: TUES. AUGUST 20, 2019
 ACTION: DENIED
  
 1) THE COVERSHEET LIST THE PROJECT DATA. THE PLAN
 INDICATES THIS NEW TENANT SPACE IS TO BE A BUSINESS
 OCCUPANCY. CURRENTLY THE SPACE IS A DRUG STORE WHICH IS
 A MERCANTILE OCCUPANCY. PLEASE SEE CHAPTER 10 OF THE
 EXISTING BUILDING CODE SECTION 1001.2.2.1 FOR PARTIAL
 CHANGE OF OCCUPANCY REQUIREMENTS. WHERE A PORTION OF A
 BUILDING IS CHANGING OCCUPANCIES SECTION 1012 OF THE
 EXISTING BUILDING CODE SHALL APPLY.
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
 2) THE SHEET A-1 SHOWS A PROPOSED BEAUTY SHOP/ HAIR
 STYLING SHOP WITH AN OCCUPANT LOAD OF 14 PEOPLE. NO
 LIFE SAFETY PLAN WAS SUBMITTED SHOWING THE EGRESS PATH
 FOR THIS TENANT SPACE. SHEET E-1 SHOWS AN EXIT LIGHT AT
 THE NEW EXTERIOR DOOR OPENING ON CLEMATIS ST. PLEASE
 SEE DOOR 2 & 5 BOTH ARE MANUALLY SLIDING DOORS, THEY
 CANNOT BE THE REQUIRED EGRESS DOORS. DOOR # 8 WILL HAVE
 TO BE THE EGRESS DOOR WITH EXIT LIGHT.
 PLEASE REVIEW THE 2017 FBC-B SECTION 1010.1.2.
 EXCEPTION # 9. EXCEPTION 9. IN OTHER THAN GROUP H
 OCCUPANCIES, MANUALLY OPERATED HORIZONTAL SLIDING DOORS
 ARE PERMITTED IN A MEANS OF EGRESS FROM SPACES WITH AN
 OCCUPANT LOAD OF 10 OR LESS.
 3A) SHEET A1 DETAIL 1 SHOWS THE TENANT WALLS EXTENDING
 UP HALFWAY TO THE CEILING. THE SCALE ON THE DRAWING
 INDICATES 1 ? INCH = 1 FOOT. IT WOULD APPEAR THIS IS A
 TYPO AND THE SCALE SHOULD READ ? INCH SCALE EQUALS 1
 FOOT. DISCREPANCY IN PLAN. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
 3B) SHEET A1 DETAIL 1 SHOWS THE TENANT WALLS EXTENDING
 UP HALFWAY TO THE CEILING. ABOVE THIS AREA THE AIR
 COMMUNICATES WITH THE EXIT CORRIDOR AND OTHER TENANT
 SPACES. IN THE 2017 FBC-B SECTION 2801.1. MECHANICAL
 APPLIANCES, EQUIPMENT AND SYSTEMS SHALL BE CONSTRUCTED,
 INSTALLED AND MAINTAINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, MECHANICAL. IN THE MECHANICAL CODE UNDER
 VENTILATION TABLE 403.3.1.1 SPECIALTY SHOPS PLEASE SEE
 BEAUTY SALON REQUIREMENTS (SEE FOOTNOTE B) FOR
 VENTILATION AND IF MANICURES AND OR PEDICURE STATIONS
 SOURCE CAPTURE SYSTEMS ARE REQUIRED AT EACH STATION,
 SEE FOOTNOTES B & H. FOOTNOTE B STATES MECHANICAL
 EXHAUST REQUIRED AND THE RECIRCULATION OF AIR FROM SUCH
 SPACES IS PROHIBITED. RECIRCULATION OF AIR THAT IS
 CONTAINED COMPLETELY WITHIN SUCH SPACES SHALL NOT BE
 PROHIBITED (SEE SECTION 403.2.1, ITEM 3).
 3C) SHEET A1 DETAIL 1 SHOWS THE TENANT WALLS EXTENDING
 UP HALFWAY TO THE CEILING. THE PLAN DOES NOT SHOW HOW
 THE TENANT SEPARATION WALLS ARE GOING TO BE PERMANENT
 AND NO FLEXING AND LEANING. 2017 FBC-B 1604.3
 SERVICEABILITY. STRUCTURAL SYSTEMS AND MEMBERS THEREOF
 SHALL BE DESIGNED TO HAVE ADEQUATE STIFFNESS TO LIMIT
 DEFLECTIONS AND LATERAL DRIFT.
 1604.3.1 DEFLECTIONS. THE DEFLECTIONS OF STRUCTURAL
 MEMBERS SHALL NOT EXCEED THE MORE RESTRICTIVE OF THE
 LIMITATIONS OF SECTIONS 1604.3.2 THROUGH 1604.3.5 OR
 THAT PERMITTED BY TABLE 1604.3.
 3D) SHEET A1 DETAIL 1 SHOWS NEW DRYWALL BEAMS SEE
 DETAIL 2/ A2. THIS DETAIL INDICATES THE NEW DRYWALL
 BEAMS ARE TO BE 10 INCHES TALL AND 2 FEET WIDE. THE
 CHARTS FROM THE STEEL STUD MANUFACTURERS ASSOCIATION
 SHOWS THE LARGEST CEILING SPAN MEMBERS AS 600S162 WHEN
 AT 2 FEET ON CENTER AND THICKNESS IN (43MILS) A SPAN OF
 15 FEET 2 INCHES AND ALLOWABLE DEFLECTION OF L/240. THE
 SAME SIZE FRAMING MEMBER AT 16 INCHES ON CENTER A SPAN
 OF 16 FEET 11 INCHES AND IF THE SPACING IS AT 12 INCHES
 ON CENTER A SPAN OF 18 FEET 4 INCHES WHEN THERE IS NO
 SUPPORT AT THE MID-POINT. PLEASE PROVIDE WHERE YOU ARE
 GETTING YOUR SPAN INFORMATION FROM? 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED. 2017 FBC-B 2211.1.
 3E) SHEET A-1 WALL LEGEND SHOWS WALL TYPE A, SEE
 SECTION 1/ A-2. THIS DETAIL SHOWS A NEW ALCOVE SET BACK
 FROM THE FRONT STOREFRONT, A NEW ENTRY. WHAT SHEET A-1
 NOR SHEET A-2 SHOW IS THE NEW WHAT APPEARS TO BE NEW
 CONCRETE COLUMNS JUST TO THE WEST OF THIS NEW ALCOVE?
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED AS TO THE
 SIZE OF THE CONCRETE COLUMN, REBAR SIZE, AND AMOUNT OF
 VERTICAL REBAR AND AT WHAT CENTER AND SIZE OF HOOPS FOR
 THIS COLUMN AS WELL AS EMBEDMENT INTO THE SLAB AND
 CONCRETE BEAM ABOVE.
 3F) SHEET A-2 SHOWS 3 DETAILS, 3, 4 & 5. DETAIL 5 SHOWS
 THE USE OF (2) 2X6 BUCKS BEING FASTENED TO STEEL BEAM
 AND COLUMNS WITH 2 INCH CREWS AT 12 INCHES ON CENTER.
 3F)(1) IS THE 2X6 BUSKS TO BE RIPPED DOWN TO BE A FULL
 4 INCHES WIDE TO BE THE SAME WIDTH AS THE 4 INCH STEEL
 BEAM? OR IS THIS A TYPO? 107.2.1.2 ADDITIONAL
 INFORMATION REQUIRED.
 3F)(2) DETAILS 3 AND 4 DO NOT SHOW THE INSTALLATION OF
 A DOUBLE BUCK ATTACHED TO THE STEEL BEAM OR COLUMN.
 107.2.1.2 ADDITIONAL INFORMATION REQUIRED.
 3F) IN DETAIL #4 & 5 IT APPEARS THE BOTTOM PLATE IS TO
 BE TURNED SIDEWAYS, THE QUESTION IS THE BOTTOM STEEL
 PLATE SUPPOSE TO SIT ON TOP OF THE CONCRETE FLOOR OR BE
 SUNKEN, IF SO HOW MUCH? 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
 4) SHEET A-2 SHOWS THE USE OF WELDED AND BOLTED
 CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD
 PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS
 FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
 5) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS
  
 6) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 7) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 8) ASBESTOS: IN ACCORDANCE WITH SECTION 553.79 F. S.
 THIS IS TO ADVISE YOU OF THE OWNERS OR OPERATORS?
 RESPONSIBILITY TO COMPLY WITH THE STATE & FEDERAL
 ASBESTOS REGULATIONS, INCLUDING SECTION 376.60 F. S.
 AND CFR 61- NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE-
 ASBESTOS SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION
 TO THE DEPARTMENT OF ENVIRONMENTAL PROTECTION PRIOR TO:
 * DEMOLITION OF ALL REGULATED STRUCTURES;
 * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES
 WHERE ASBESTOS IS DISTURBED OR REMOVED.
 NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY.
  
 FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT
 THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING
 HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT
 (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR
 POLLUTION CONTROL SECTION)
  
 901 EVERNIA STREET
 WEST PALM BEACH, FL 33401
 (561) 355-3070
  
 9) PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE.
 CALL (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT
 ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC
 TFEES/FORMS/QUESTIONNAIRE.PDF
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
2019-08-20 14:52:49BUILDING REVIEW IN PROGRESS.