2019-09-12 15:40:54PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 THIS PROJECT IS A CHANGE OF USE WITH NO CHANGE OF
 OCCUPANCY CLASSIFICATION FBC EXISTING BUILDING SECTION
 1001.2.1
  
 1) SUBMIT TWO SETS OF ENERGY CODE COMPLIANCE FORMS AS
 REQUIRED BY FBC ENERGY CONSERVATION SECTION R101.5.1.
  
 2) SPECIFY THE BUILDINGS THERMAL ENVELOPE ON THE PLANS.
 INDICATE THE INSULATION MATERIAL AND R-VALUE OF THE
 CEILING INSULATION. FBC ENERGY CONSERVATION R103.2
  
 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 WINDOW TYPES AND EXTERIOR DOOR TYPES.
  
 4) SHOW THAT SECTION 6 ON SHEET S-2G IS IN COMPLIANCE
 WITH FBC-R318.7 INSPECTION FOR TERMITES. IN ORDER TO
 PROVIDE FOR INSPECTION FOR TERMITE INFESTATION,
 CLEARANCE BETWEEN EXTERIOR WALL COVERINGS AND FINAL
 EARTH GRADE ON THE EXTERIOR OF A BUILDING SHALL NOT BE
 LESS THAN 6 INCHES (152 MM).
 EXCEPTIONS:
 3.A 4-INCH (102 MM) INSPECTION SPACE ABOVE PATIO AND
 GARAGE SLABS AND ENTRY AREAS.
  
 5) VERIFY THE ROOF TO WALL CONNECTIONS AND MITIGATE IF
 REQUIRED. FBC-R301.1 APPLICATION. BUILDINGS AND
 STRUCTURES, AND PARTS THEREOF, SHALL BE CONSTRUCTED TO
 SAFELY SUPPORT ALL LOADS, INCLUDING DEAD LOADS, LIVE
 LOADS, ROOF LOADS, FLOOD LOADS, SNOW LOADS, WIND LOADS
 AND SEISMIC LOADS AS PRESCRIBED BY THIS CODE. THE
 CONSTRUCTION OF BUILDINGS AND STRUCTURES IN ACCORDANCE
 WITH THE PROVISIONS OF THIS CODE SHALL RESULT IN A
 SYSTEM THAT PROVIDES A COMPLETE LOAD PATH THAT MEETS
 THE REQUIREMENTS FOR THE TRANSFER OF LOADS FROM THEIR
 POINT OF ORIGIN THROUGH THE LOAD-RESISTING ELEMENTS TO
 THE FOUNDATION. BUILDINGS AND STRUCTURES CONSTRUCTED AS
 PRESCRIBED BY THIS CODE ARE DEEMED TO COMPLY WITH THE
 REQUIREMENTS OF THIS SECTION.
  
 6) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
  
  
  