Plan Review Notes
Plan Review Notes For Permit 19080314
Permit Number 19080314
Review Stop P
Sequence Number 1
Notes
Date Text
2019-08-22 12:57:4708/22/2018 1ST PLUMBING REVIEW **DENIED** WITH
 COMMENTS.
  
 NOTE: A FULL AND COMPREHENSIVE PLAN REVIEW COULD NOT BE
 ACCOMPLISHED AT THIS TIME DUE TO THE QUALITY OF THE
 SUBMITTED PLANS. ADDITIONAL COMMENTS MAY BE GENERATED
 ON THE RESUBMITTAL REVIEW.
  
 1. WATER HEATER EF 0.624 ON A 75 GALLON ON FORM
 R405-2017 IS NOT CORRECT ACCORDING TO NATIONAL
 APPLIANCE ENERGY CONSERVATION ACT FOR HOT WATER
 REGULATION 2015 AND IT SHOULD BE AT EF 0.74, SEE THE
 COMPLETE STANDARD 10 CFR 430.32(D) FOR ALL DETAILS.
  
 2. ON THE ISOMETRIC DRAWING PA-1 THE WATER CLOSET NEEDS
 TO BE VENTED BY A WET VENT PER THE 2017 FBC RES SEC.
 3108.2.1HORIZONTAL WET VENT.
  
 3. GAS REVIEW AND PERMIT APPLICATION REQUIRED FOR WATER
 HEATER AND GRILL PER THE 2017 WPB AMENDMENTS TO FBC
 SEC. 107.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  