| Plan Review Notes For Permit 19080314 |
| Permit Number |
19080314 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-08-22 12:57:47 | 08/22/2018 1ST PLUMBING REVIEW **DENIED** WITH | | | COMMENTS. | | | | | | NOTE: A FULL AND COMPREHENSIVE PLAN REVIEW COULD NOT BE | | | ACCOMPLISHED AT THIS TIME DUE TO THE QUALITY OF THE | | | SUBMITTED PLANS. ADDITIONAL COMMENTS MAY BE GENERATED | | | ON THE RESUBMITTAL REVIEW. | | | | | | 1. WATER HEATER EF 0.624 ON A 75 GALLON ON FORM | | | R405-2017 IS NOT CORRECT ACCORDING TO NATIONAL | | | APPLIANCE ENERGY CONSERVATION ACT FOR HOT WATER | | | REGULATION 2015 AND IT SHOULD BE AT EF 0.74, SEE THE | | | COMPLETE STANDARD 10 CFR 430.32(D) FOR ALL DETAILS. | | | | | | 2. ON THE ISOMETRIC DRAWING PA-1 THE WATER CLOSET NEEDS | | | TO BE VENTED BY A WET VENT PER THE 2017 FBC RES SEC. | | | 3108.2.1HORIZONTAL WET VENT. | | | | | | 3. GAS REVIEW AND PERMIT APPLICATION REQUIRED FOR WATER | | | HEATER AND GRILL PER THE 2017 WPB AMENDMENTS TO FBC | | | SEC. 107.2.1. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | |
|