Plan Review Notes
Plan Review Notes For Permit 19080314
Permit Number 19080314
Review Stop NFIP
Sequence Number 1
Notes
Date Text
2019-09-11 17:09:39NFIP REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CITY OF WEST PALM BEACH ORDINANCE NO. 4658-16
 AS OF OCTOBER 5, 2017, THE FEDERAL EMERGENCY MANAGEMENT
 AGENCY (FEMA) ESTABLISHED A NEW FLOOD INSURANCE RATE
 MAP (FIRM) UTILIZING THE RECENTLY COMPLETED FLOOD
 HAZARD DETERMINATION (FHD) FOR THE CITY OF WEST PALM
 BEACH, FL.
 ALL NEW BASE FLOOD ELEVATIONS (BFE) SHALL BE BASED ON
 NAVD88 DATUM. ON AUGUST 23, 2017, THE CITY OF WEST PALM
 BEACH, BY ORDINANCE, NO. 4658-16, ESTABLISHED A TWO
 FOOT FREEBOARD ABOVE THE (BFE).
  
 1. BASED ON THE SUBMITTED SURVEY, THIS LOT AND PROPOSED
 IMPROVEMENTS ARE LOCATED IN AN AE FLOOD ZONE WITH A
 BASE FLOOD ELEVATION (BFE) OF 6.0 FEET NAVD.
 2. AS OF OCTOBER 5, 2017, THE FEDERAL EMERGENCY
 MANAGEMENT AGENCY (FEMA) ESTABLISHED A NEW FLOOD
 INSURANCE RATE MAP (FIRM) UTILIZING THE RECENTLY
 COMPLETED FLOOD HAZARD DETERMINATION (FHD) FOR THE CITY
 OF WEST PALM BEACH, FL.
 3. ALL NEW BASE FLOOD ELEVATIONS (BFE) SHALL BE BASED
 ON NAVD88 DATUM. ON AUGUST 23, 2017, THE CITY OF WEST
 PALM BEACH, BY ORDINANCE, ESTABLISHED A TWO FOOT
 FREEBOARD ABOVE THE (BFE).
 4. YOU MAY SUBMIT A SURVEY SHOWING ALL EXISTING AND
 PROPOSED ELEVATIONS BASED ON NAVD88 DATUM PLUS TWO FEET
 OF FREEBOARD OR THE ENGINEER OF RECORD (EOR) MAY ADD A
 STATEMENT TO THE STRUCTURAL PLAN THAT THE DESIGN FLOOD
 ELEVATION (DFE) WILL BE 8.0 FEET NAVD88 BASED ON THE
 (BFE) OF 6.00 FEET FOR FLOOD ZONE AE.
  
 ELEVATION CERTIFICATE COMMENTS
  
 1. SECTION A9 (B) NUMBER OF FLOOD OPENINGS REQUIRED.
 2. SECTION A9 (C) NET AREA OF FLOOD OPENINGS
 3. SECTION A9 (D) NON-ENGINEERED OPENINGS HAVE BEEN
 SELCTED. PROVIDE PRODUCT APPROVALS FOR FLOOD VENTS.
 4. C2 (A) TOP OF BOTTOM FLOOR IS LISTED AS 7.0 FEET
 NAVD. MINIMUM ELEVATION SHALL BE 8.0 FEET NAVD.
 5. C2 (B) TOP OF BEAM LISTED AS 21.0 FEET NAVD. SHOULD
 BE 22 FEET 4 INCHES.
 6. C2 (D) ELEVATION LISTED AS 7.0 FEET NAVD. FLOOD
 VENTS REQUIRED.
 7. C2 (E) LOWEST ELEVATION OF EQUIPMENT SHALL BE THE
 DESIGN FLOOD ELEVATION (DFE) OF 8 FEET NAVD.
  
  
  
  
  
  