Plan Review Notes
Plan Review Notes For Permit 19080310
Permit Number 19080310
Review Stop P
Sequence Number 1
Notes
Date Text
2019-08-22 14:15:59PLUMBING COMMEMTS: APPROVED W/PROVISO
  
 1. PER WPB FBC 107.2.1 AND 107.3.4.1, SUBMIT AS A
 DEFERRED SUBMITTAL CROSS SECTIONAL DETAIL OF SHOWER
 CONSTRUCTION SHOWING COMPLIANCE WITH FBC PL SECTION
 417. BOTH SHOWERS SHALL BE RECONSTRUCTED TO COMPLY.
 SUBMITTAL SHALL BE SUBMITTED, APPROVED AND IN PLACE
 PRIOR TO FIRST PLUMBING INSPECTION. SEE WPB FBC
 107.3.4.1 BELOW.
  
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY
 SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE
 BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED
 AND FOUND TO BE IN GENERAL CONFORMANCE TO THE DESIGN OF
 THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  