| Date |
Text |
| 2020-11-04 10:24:46 | PLAN REVIEW / BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | NEC 2014 |
| | |
| | 3RD REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. |
| | PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED |
| | SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN |
| | PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER |
| | PREVIOUS COMMENTS. |
| | |
| | 2ND REVIEW COMMENTS: |
| | |
| | ADDITION AND GUEST HOUSE 19080288 AND 19090434 |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) PLEASE PROVIDE THE MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE ROOFING SYSTEMS TO BE USED. |
| | (NOT ADDRESSED) |
| | 2) PLEASE PROVIDE THE MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVAL FOR THE MULL BAR FOR THE CONNECTION OF |
| | THE 2 WINDOWS MARKED "W4" MASTER BEDROOM. (NOT |
| | ADDRESSED) |
| | 3) PLEASE SHOW THE WALL AND CEILING INSULATION "R" |
| | VALUE AND INSULATION TYPE TO MATCH THE ENERGY CALCS. |
| | (ENERGY CALCS NOT YET PROVIDED). CORRECTED |
| | 4) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE SLIDING GLASS DOORS AND |
| | EXTERIOR SWING DOORS ( DOCUMENTS PROVIDED FOR THE |
| | EXTERIOR SWING DOOR IS NOT A COMPLETE MIAMI DADE OR |
| | FLORIDA STATE PRODUCT APPROVAL) (NOT ADDRESSED) |
| | 5) DRAWING A2 - PLEASE CHECK THE WINDOW AND DOOR |
| | SCHEDULE - MARKS W4, W7 AND D1 DO NOT MATCH THE FLOOR |
| | PLAN. CORRECTED |
| | 6) GUEST HOUSE EGRESS DOOR WIDTH AT 32 INCHES IS NOT A |
| | WIDE ENOUGH OPENING - WIDTH NEEDS TO COMPLY WITH FBC |
| | R311.2 EGRESS DOOR. CORRECTED |
| | NOT LESS THAN ONE EGRESS DOOR SHALL BE PROVIDED FOR |
| | EACH DWELLING UNIT. THE EGRESS DOOR SHALL BE |
| | SIDE-HINGED, AND SHALL PROVIDE A CLEAR WIDTH OF NOT |
| | LESS THAN 32 INCHES (813 MM) WHERE MEASURED BETWEEN THE |
| | FACE OF THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 |
| | DEGREES. |
| | |