| 2019-08-07 15:05:59 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE IS NO FLOOR PLAN SHEET LOCATING THE PROPOSED |
| | INSTALLATION. |
| | |
| | PLEASE PROVIDE A DETAILED FLOOR PLAN INCLUDING |
| | DIMENSIONS. |
| | |
| | |
| | |
| | 2) THERE ARE ONLY LIMITED SHEETS PROVIDED FOR THE |
| | PROPOSED EQUIPMENT. |
| | |
| | PAGES ARE MISSING, |
| | |
| | PLEASE PROVIDE THE ENTIRE SPEC SHEET PACKET WITH ALL |
| | PAGES TO CONFIRM ALL SPECS ARE MET. |
| | |
| | |
| | |
| | 3) WHAT IS THE POWER SOURCE FOR THE PROPOSED. |
| | |
| | PLEASE PROVIDE THE WIRING DIAGRAMS AND LOCATIONS AND |
| | SIZE OF EXISTING POWER SOURCE. |
| | |
| | |
| | |
| | 4) THERE IS NO INDICATION OF A AUTOMATIC SHUT OFF AS |
| | PER NFPA 96. |
| | |
| | PER NFPA 96 |
| | |
| | 10.5 MANUAL ACTIVATION. |
| | 10.5.1 A READILY ACCESSIBLE MEANS FOR MANUAL ACTIVATION |
| | SHALL |
| | BE LOCATED BETWEEN 1067 MM AND 1219 MM (42 IN. AND 48 |
| | IN.) |
| | ABOVE THE FLOOR, BE ACCESSIBLE IN THE EVENT OF A FIRE, |
| | BE LOCATED |
| | IN A PATH OF EGRESS, AND CLEARLY IDENTIFY THE HAZARD |
| | PROTECTED. |
| | 10.5.1.1 AT LEAST ONE MANUAL ACTUATION DEVICE SHALL BE |
| | LOCATED |
| | A MINIMUM OF 3 M (10 FT) AND A MAXIMUM OF 6 M (20 FT) |
| | FROM |
| | THE PROTECTED HOOD EXHAUST SYSTEM(S) WITHIN A PATH OF |
| | EGRESS |
| | OR AT AN ALTERNATIVE LOCATION ACCEPTABLE TO THE AHJ. |
| | 10.5.1.2 MANUAL ACTIVATION USING A CABLE-OPERATED PULL |
| | STATION |
| | SHALL NOT REQUIRE MORE THAN 178 N (40 LB) OF FORCE, |
| | WITH A |
| | PULL MOVEMENT NOT TO EXCEED 356 MM (14 IN.) TO ACTIVATE |
| | THE |
| | AUTOMATIC FIRE-EXTINGUISHING EQUIPMENT. |
| | 10.5.2 THE AUTOMATIC AND MANUAL MEANS OF SYSTEM |
| | ACTIVATION |
| | EXTERNAL TO THE CONTROL HEAD OR RELEASING DEVICE SHALL |
| | BE SEPARATE |
| | AND INDEPENDENT OF EACH OTHER SO THAT FAILURE OF ONE |
| | WILL NOT |
| | IMPAIR THE OPERATION OF THE OTHER EXCEPT AS PERMITTED |
| | BY 10.5.3. |
| | |
| | PLEASE REVIEW, PROVIDE AND INCLUDE LOCATION ON FLOOR |
| | PLAN. |
| | |
| | |
| | |
| | 5) THERE IS NO INDICATION OF SYSTEM ACTIVATION PER NFPA |
| | 96 |
| | |
| | 10.6 SYSTEM ANNUNCIATION. |
| | 10.6.1 UPON ACTIVATION OF AN AUTOMATIC |
| | FIRE-EXTINGUISHING SYSTEM, |
| | AN AUDIBLE ALARM OR VISUAL INDICATOR SHALL BE PROVIDED |
| | TO |
| | SHOW THAT THE SYSTEM HAS ACTIVATED. |
| | 10.6.2 WHERE A FIRE ALARM SIGNALING SYSTEM IS SERVING |
| | THE OCCUPANCY |
| | WHERE THE EXTINGUISHING SYSTEM IS LOCATED, THE |
| | ACTIVATION |
| | OF THE AUTOMATIC FIRE-EXTINGUISHING SYSTEM SHALL |
| | ACTIVATE |
| | THE FIRE ALARM SIGNALING SYSTEM. |
| | |
| | |
| | PLEASE REVIEW AND PROVIDE. |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |