Plan Review Notes
Plan Review Notes For Permit 19080244
Permit Number 19080244
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-08-07 15:05:59THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO FLOOR PLAN SHEET LOCATING THE PROPOSED
 INSTALLATION.
  
 PLEASE PROVIDE A DETAILED FLOOR PLAN INCLUDING
 DIMENSIONS.
  
  
  
 2) THERE ARE ONLY LIMITED SHEETS PROVIDED FOR THE
 PROPOSED EQUIPMENT.
  
 PAGES ARE MISSING,
  
 PLEASE PROVIDE THE ENTIRE SPEC SHEET PACKET WITH ALL
 PAGES TO CONFIRM ALL SPECS ARE MET.
  
  
  
 3) WHAT IS THE POWER SOURCE FOR THE PROPOSED.
  
 PLEASE PROVIDE THE WIRING DIAGRAMS AND LOCATIONS AND
 SIZE OF EXISTING POWER SOURCE.
  
  
  
 4) THERE IS NO INDICATION OF A AUTOMATIC SHUT OFF AS
 PER NFPA 96.
  
 PER NFPA 96
  
 10.5 MANUAL ACTIVATION.
 10.5.1 A READILY ACCESSIBLE MEANS FOR MANUAL ACTIVATION
 SHALL
 BE LOCATED BETWEEN 1067 MM AND 1219 MM (42 IN. AND 48
 IN.)
 ABOVE THE FLOOR, BE ACCESSIBLE IN THE EVENT OF A FIRE,
 BE LOCATED
 IN A PATH OF EGRESS, AND CLEARLY IDENTIFY THE HAZARD
 PROTECTED.
 10.5.1.1 AT LEAST ONE MANUAL ACTUATION DEVICE SHALL BE
 LOCATED
 A MINIMUM OF 3 M (10 FT) AND A MAXIMUM OF 6 M (20 FT)
 FROM
 THE PROTECTED HOOD EXHAUST SYSTEM(S) WITHIN A PATH OF
 EGRESS
 OR AT AN ALTERNATIVE LOCATION ACCEPTABLE TO THE AHJ.
 10.5.1.2 MANUAL ACTIVATION USING A CABLE-OPERATED PULL
 STATION
 SHALL NOT REQUIRE MORE THAN 178 N (40 LB) OF FORCE,
 WITH A
 PULL MOVEMENT NOT TO EXCEED 356 MM (14 IN.) TO ACTIVATE
 THE
 AUTOMATIC FIRE-EXTINGUISHING EQUIPMENT.
 10.5.2 THE AUTOMATIC AND MANUAL MEANS OF SYSTEM
 ACTIVATION
 EXTERNAL TO THE CONTROL HEAD OR RELEASING DEVICE SHALL
 BE SEPARATE
 AND INDEPENDENT OF EACH OTHER SO THAT FAILURE OF ONE
 WILL NOT
 IMPAIR THE OPERATION OF THE OTHER EXCEPT AS PERMITTED
 BY 10.5.3.
  
 PLEASE REVIEW, PROVIDE AND INCLUDE LOCATION ON FLOOR
 PLAN.
  
  
  
 5) THERE IS NO INDICATION OF SYSTEM ACTIVATION PER NFPA
 96
  
 10.6 SYSTEM ANNUNCIATION.
 10.6.1 UPON ACTIVATION OF AN AUTOMATIC
 FIRE-EXTINGUISHING SYSTEM,
 AN AUDIBLE ALARM OR VISUAL INDICATOR SHALL BE PROVIDED
 TO
 SHOW THAT THE SYSTEM HAS ACTIVATED.
 10.6.2 WHERE A FIRE ALARM SIGNALING SYSTEM IS SERVING
 THE OCCUPANCY
 WHERE THE EXTINGUISHING SYSTEM IS LOCATED, THE
 ACTIVATION
 OF THE AUTOMATIC FIRE-EXTINGUISHING SYSTEM SHALL
 ACTIVATE
 THE FIRE ALARM SIGNALING SYSTEM.
  
  
 PLEASE REVIEW AND PROVIDE.
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  