Plan Review Notes
Plan Review Notes For Permit 19080234
Permit Number 19080234
Review Stop P
Sequence Number 1
Notes
Date Text
2019-08-12 11:09:161) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN
 DRAIN. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE
 MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM
 ITS PUMP CURVE AND THE SIMPLIFIED TOTAL DYNAMIC HEAD
 CALCULATION IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC
 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 EDITION
 ADDRESSES FLOW RATE IN GALLONS PER MINUTE (GPM). IT
 REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED
 THE LISTED MAXIMUM FLOW RATE OF THE SUCTION OUTLET
 FITTING ASSEMBLY (DRAIN COVER).THE TDH CALCULATIONS
 MUST INCLUDE ALL OF THE SYSTEM COMPONENTS INCLUDING
 SUCTION AND RETURN PIPING, FITTINGS, VALVES, HEATER,
 FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS EXCEPT
 THE PUMP.
 3) SUBMIT TWO LEGIBLE COPIES OF THE SPA PUMP CURVE.
 IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC
 TO THE PUMP BEING INSTALLED ON THIS POOL. THIS IS
 NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH
 CALCULATIONS. ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9,
 4.4.9.1
 4) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE POOL PUMP. INDICATE ON THE POOL
 PUMP SPECS WHICH PUMP IS BEING INSTALLED. WPB AMEND. TO
 FBC SEC. 107.2.1.
 5) SUBMIT A LEGIBLE SHEET FOR THE FRICTION FLOW DATA.
 WPB AMEND. TO FBC SEC. 107.2.1.
 6) SHOW THE TURNOVER RATE FOR THE SPA ON THE PLANS.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW