Plan Review Notes
Plan Review Notes For Permit 19080176
Permit Number 19080176
Review Stop P
Sequence Number 1
Notes
Date Text
2019-08-27 15:52:06CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
  
 PLUMBING COMMEMTS: DENIED
  
 1. PROVIDE DETAIL AND CLEAR FLOOR SPACE FOR WASHER AND
 DRYER TO SHOW COMPLIANCE WITH FBC ACC 611
  
 2. SHOW DIMENSIONS AND LABEL OF ALL REQUIRED FLOOR
 SPACES INCLUDING THOSE FOR EWC AND BREAKROOM SINK
 ADDITION TO THE BATHROOM FIXTURES AND WASHER/ DRYER AS
 REQUIRED IN FBC ACC CHAPTER 3.
  
 3. PLAN SHEET A-2:
  
 A. GRAB BARS SHALL BE MEASURED FROM FINISH FLOOR TO THE
 TOP OF THE GRIPPING SURFACE AT 33" MIN- 36" MAX. PER
 FBC ACC 609.4
  
 B. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION PER FBC ACC 604.2
  
 4. ICE MAKER SHALL CONNECT TO THE SANITARY THROUGH AN
 AIR GAP INTO A TRAPPED AND VENTED WASTE RECEPTACLE PER
 FBC PL 802.2.
  
 5. 3? FIXTURE DRAIN FROM FLOOR DRAIN TRAP TO VENT SHALL
 NOT EXCEED 12? PER FBC PL 909.1.
  
 6. PROVIDE THERMAL EXPANSION DEVICE REQUIRED ON COLD
 WATER SUPPLY TO TANK TYPE WATER HEATER. A MEANS FOR
 CONTROLLING INCREASED PRESSURE CAUSED BY THERMAL
 EXPANSION SHALL BE INSTALLED FBC PL 607.3
  
 7. IS WATER HEATER MOUNTED ON THE FLOOR ORABOVE THE
 FLOOR. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR WATER
 HEATER SHOWING HOW HEATER WILL BE STRUCTURALLY
 SUPPORTED IF LOCATED ABOVE THE FLOOR. PROVIDE DIRECTION
 FOR EMERGENCY PAN DRAIN TO A POINT OF TERMINATION.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19080176 3220 45TH ST
  