Plan Review Notes
Plan Review Notes For Permit 19080176
Permit Number 19080176
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-08-06 14:44:46THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE DOES NOT APPEAR TO BE A CLEAR SCOPE OF WORK.
 THERE IS A SHADED AREA IDENTIFIED AS NOT IN SCOPE, YET
 IT APPEARS THAT MEZZANINE STAIRS ARE BEING RELOCATED IN
 THAT SPACE.
  
 IS THIS PROPOSED PROJECT SEPARATING TWO SEPARATE
 SPACES?
  
 PLEASE PROVIDE DETAILS INCLUDING ANY AND ALL WORK
 ASSOCIATED WITH THE ADJACENT SPACE.
  
  
  
 2) SHEET A 1 & A 3- THERE IS A SEPARATION WALL
 INDICATED AS W 7 WHICH IS NOT INDICATED AS HAVING A
 RATED LISTING ON SHEET A 3.
  
 PLEASE REIVEW AND OR CORRECT
  
  
  
 3) SHEET A 1 & A 3 - THE RATED WALL DETAILS AT THE
 OFFICE AREAS DO NOT INDICATE CONTIUNITY OF THE
 CONSTRUCTION FROM THE FLOOR UP TO FLOORING/DECKING,
 THROUGH THE FLOORING/DECKING AND ABOVE THE MEZZANINCE
 TO THE UNDERSIDE OF THE ROOF.
  
 PLEASE PROVIDE DETAILS TO ENSURE CONTINOUS CONSTRUCTION
 FEATURES.
  
  
  
 4) SHEET LS 1 - THERE DOES NOT APPEAR TO BE EXIT SIGNS
 ONCE ENTRANCE TO THE STORAGE AREA IS MADE FROM THE
 OFFICE AREA. HOWEVER, A FEW DO APPEAR ON SHEETS A 1 AND
 E 2.
  
 PER NFPA 101, CH 7, MEANS OF EGRESS
  
 7.10 MARKING OF MEANS OF EGRESS.
 7.10.1 GENERAL.
 7.10.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE
 MARKED IN
 ACCORDANCE WITH SECTION 7.10 WHERE REQUIRED IN CHAPTERS
 11
 THROUGH 43.
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS.
  
 7.10.1.5 EXIT ACCESS.
 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED,
 READILY
 VISIBLE SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO
 REACH THE EXIT IS
 NOT READILY APPARENT TO THE OCCUPANTS.
 7.10.1.5.2* NEW SIGN PLACEMENT SHALL BE SUCH THAT NO
 POINT IN AN
 EXIT ACCESS CORRIDOR IS IN EXCESS OF THE RATED VIEWING
 DISTANCE OR
 100 FT (30 M), WHICHEVER IS LESS, FROM THE NEAREST
 SIGN.
  
 ADDITIONAL EXIT SIGNAGE MAY BE REQUIRED IF RACKS OR
 EQUIPMENT IS PROPOSED IN THIS OPEN STORAGE SPACE.
  
 PLEASE REVIEW, CORRECT WHERE NEEDED TO BE CONSISTENT
 AND PROVIDE AS REQUIRED.
  
  
  
 5) SHEET A 1 - THERE IS A NOTE INDICATING NEW GUARDRAIL
 WITH NO DETAILS.
  
 7.2.2.4.6.1 THE HEIGHT OF GUARDS REQUIRED IN 7.1.8
 SHALL BE
 MEASURED VERTICALLY TO THE TOP OF THE GUARD FROM THE
 SURFACE
 ADJACENT THERETO.
 7.2.2.4.6.2 GUARDS SHALL BE NOT LESS THAN 42 IN. (1065
 MM) HIGH,
 EXCEPT AS PERMITTED BY ONE OF THE FOLLOWING:
 (1) EXISTING GUARDS WITHIN DWELLING UNITS SHALL BE
 PERMITTED TO
 BE NOT LESS THAN 36 IN. (915 MM) HIGH.
 (2) THE REQUIREMENT OF 7.2.2.4.6.2 SHALL NOT APPLY IN
 ASSEMBLY
 OCCUPANCIES WHERE OTHERWISE PROVIDED IN CHAPTERS 12 AND
 13.
 (3) *EXISTING GUARDS ON EXISTING STAIRS SHALL BE
 PERMITTED TO BE
 NOT LESS THAN 30 IN. (760 MM) HIGH.
  
 PLEASE PROVIDE DETAILS IN COMPLAINCE WITH NFPA 101.
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  