Plan Review Notes
Plan Review Notes For Permit 19080176
Permit Number 19080176
Review Stop B
Sequence Number 1
Notes
Date Text
2019-08-27 07:57:302017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19080176
 ADD: 3220 45TH ST.
 CONT: DEAN MITCHELL GROUP
 TEL: 561-262-9779
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. AUGUST 27TH/ 2019
 ACTION: DENIED
 1) SHEET LS-1, THE LIFE SAFETY SHEET:
 1A). THIS SET OF PLANS INDICATES GOING FROM A SINGLE
 TENANT TO TWO TENANTS BUT THE WHOLE BUILDING IS NOT
 BEING SHOWN IT APPEARS THERE IS A CREATION OF
 NONCONFORMITY TO THE BUILDING CODE. PLEASE PROVIDE AREA
 CALCULATIONS FOR BOTH TENANT SPACE A & B OFFICE AREA,
 STORAGE AND MEZZANINE AREAS FOR BOTH TENANTS TO ENSURE
 THAT THERE IS NO NONCONFORMITY FOR EITHER SPACE.
 2017 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING. CREATION OR EXTENSION
 OF NONCONFORMITY. ALL NEW WORK, RE-CONFIGURATION SHALL
 NOT CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING
 BUILDING TO WHICH THE RE-CONFIGURATION OF SPACE IS
 BEING MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL
 STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY
 OF MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS.
  
 1B) IN THE NEWLY CREATED TENANT SPACE B WITH THE NEW
 OFFICE AREA ON THE 1ST FLOOR AND DRY STORAGE ROOM 123
 YOU NO LONGER HAVE A MEZZANINE BUT HAVE CREATED A 2
 STORY BUILDING. PLEASE REVIEW THE 2017 FBC-B SECTION
 505.2.1. AREA LIMITATION. THE AGGREGATE AREA OF A
 MEZZANINE OR MEZZANINES WITHIN A ROOM SHALL BE NOT
 GREATER THAN ONE-THIRD OF THE FLOOR AREA OF THAT ROOM
 OR SPACE IN WHICH THEY ARE LOCATED. THE ENCLOSED
 PORTION OF A ROOM SHALL NOT BE INCLUDED IN A
 DETERMINATION OF THE FLOOR AREA OF THE ROOM IN WHICH
 THE MEZZANINE IS LOCATED. IN DETERMINING THE ALLOWABLE
 MEZZANINE AREA, THE AREA OF THE MEZZANINE SHALL NOT BE
 INCLUDED IN THE FLOOR AREA OF THE ROOM.
  
 1C) THE 3RD ISSUE IS WITH THE COMMON PATH OF TRAVEL FOR
 THE MEZZANINE/ 2ND FLOOR LEVEL. TO MEASURE COMMON PATH
 OF TRAVEL YOU MEASURE 2 FEET OF THE WALL AND FOLLOW THE
 WALL LINE. WHEN YOU GO TO THE STAIRS YOU MEASURE
 PARALLEL TO THE RISE AND RUN OF THE STAIRS. WHEN YOU
 MEASURE THE COMMON PATH OF TRAVEL IN THIS FASHION YOU
 END UP WITH APPROXIMATELY 106 FEET. PLEASE NOTE FOR
 THIS REVIEW THE AREA IN QUESTION WILL BE CONSIDERED A
 2ND STORY. IN SAYING SUCH, PLEASE REVIEW STORIES WITH
 ONE EXIT OR ACCESS TO ONE EXIT FOR OTHER OCCUPANCIES
 SEE TABLE 1006.3.2(2) (FIRST FLOOR ABOVE OR BELOW GRADE
 PLANE, NOT AT GRADE). FOR A STORAGE OCCUPANCY THE
 MAXIMUM COMMON PATH OF EGRESS TRAVEL DISTANCE IS 75
 FEET. A SECOND MEANS OF EGRESS IS NEEDED FROM THIS
 SPACE, THE NEWLY FORMED TENANT SPACE B. AT THIS TIME WE
 CANNOT COMMENT ON IF THERE IS ISSUES FOR TENANT A.
 CREATION OR EXTENSION OF NONCONFORMITY. 2017 EXISTING
 BUILDING CODE LEVEL II 701.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING. CREATION OR EXTENSION OF
 NONCONFORMITY. ALL NEW WORK, RE-CONFIGURATION SHALL NOT
 CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING
 BUILDING TO WHICH THE RE-CONFIGURATION OF SPACE IS
 BEING MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL
 STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY
 OF MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS.
  
 1D) THE LIFE SAFETY PLAN THE TOTAL SQUARE FOOTAGE IS
 STATED AT 9908 SQ. FT. BUT THE OCCUPANT LOAD IS STATED
 AT 91 SHOULD BE 99 OCCUPANTS. PLEASE REVIEW TABLE
 1004.1.2 FOR BOTH BUSINESS AND STORAGE OCCUPANCIES THE
 OCCUPANT LOAD FACTOR IS TO BE TAKEN AT GROSS SQUARE
 FEET. SEE DEFINITIONS: IBC-B 2015 CODE COMMENTARY .THE
 GROSS FLOOR AREA IS THAT AREA MEASURED WITHIN THE
 PERIMETER FORMED BY THE INSIDE SURFACE OF THE EXTERIOR
 WALLS. THE AREA OF ALL OCCUPIABLE SPACES AND
 NONOCCUPIABLE SPACES, INCLUDING MECHANICAL & ELEVATOR
 SHAFTS, TOILET ROOMS, CLOSETS AND MECHANICAL EQUIPMENT
 ROOM. PLEASE UPDATE THE PLAN.
  
 1E) PLEASE UPDATE THE LIFE SAFETY PLAN SHOWING WHERE
 THE ADDITIONAL OCCUPANTS WILL BE EXITING. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 1F) THE LIFE SAFETY PLAN UNDER THE HEADING LIFE SAFETY
 NOTES SHOW A NOTE # 8 THAT SPEAKS ABOUT SPRAY PAINT
 BOOTHS. WILL THERE BE SPRAY PAINT BOOTHS AND OTHER
 APPLICATIONS OF FLAMMABLE FINISHES THAT WILL NEED TO
 SHOW COMPLIANCE WITH THE 2017 FBC-B SECTION 416?
  
 1G) AS THE PLANS ARE DRAWN NOW THE STORAGE AREAS AND
 THE 2ND FLOOR AREA ALSO BEING OPEN TO THE 1ST FLOOR IS
 TO BE CONSIDERED A 2STORY ATRIUM.
 SECTION 202 DEFINITIONS. ATRIUM. AN OPENING CONNECTING
 TWO OR MORE STORIES OTHER THAN ENCLOSED STAIRWAYS,
 ELEVATORS, HOISTWAYS, ESCALATORS, PLUMBING, ELECTRICAL,
 AIR-CONDITIONING OR OTHER EQUIPMENT, WHICH IS CLOSED AT
 THE TOP AND NOT DEFINED AS A MALL. STORIES, AS USED IN
 THIS DEFINITION, DO NOT INCLUDE BALCONIES WITHIN
 ASSEMBLY GROUPS OR MEZZANINES THAT COMPLY WITH SECTION
 505.
  
 1H) PLEASE CONSIDER THE FOLLOWING REQUIREMENTS FOR
 ATRIUMS.
 FBC-B 404.9.3 EXIT ACCESS TRAVEL DISTANCE AT OTHER THAN
 THE LEVEL OF EXIT DISCHARGE. WHERE THE PATH OF EGRESS
 TRAVEL IS NOT AT THE LEVEL OF EXIT DISCHARGE FROM THE
 ATRIUM, THAT PORTION OF THE TOTAL PERMITTED EXIT ACCESS
 TRAVEL DISTANCE THAT OCCURS WITHIN THE ATRIUM SHALL BE
 NOT GREATER THAN 200 FEET (60 960 MM).
 404.10 INTERIOR EXIT STAIRWAYS. A MAXIMUM OF 50 PERCENT
 OF INTERIOR EXIT STAIRWAYS ARE PERMITTED TO EGRESS
 THROUGH AN ATRIUM ON THE LEVEL OF EXIT DISCHARGE IN
 ACCORDANCE WITH SECTION 1028.
  
 1I) PLEASE ALSO REVIEW THE REQUIREMENTS FOR ENCLOSURE
 OF ATRIUMS AND EXCEPTIONS. PLEASE SEE 404.6 ENCLOSURE
 OF ATRIUMS.
  
 2) SHEET A-1 THE NEW OFFICE AND STORAGE AREAS SHOW A
 WALL IDENTIFICATION TAG W-3 WHEREAS ON SHEET A-2 THERE
 IS A WALL SECTION DETAIL 07/A3 WHICH IS CORRECT? DETAIL
 07 SHOWS EXISTING FULL LENGTH STUDS AND AN EXISTING
 CEILING. 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
 DISCREPANCY IN PLANS.
  
 3) SHEET A-3 DETAIL # 3 INDICATES THE USE OF R-19
 INSULATION LAID DIRECTLY ON TOP OF THE NEW ACOUSTICAL
 CEILING. PLEASE REVIEW THE 2017 ENERGY CODE, COMMERCIAL
 C402.2.2 INSULATION INSTALLED ON A SUSPENDED CEILING
 WITH REMOVALABLE CEILING TILES SHALL NOT BE CONSIDERED
 PART OF THE MINIMUM THERMAL RESISTANCE OF THE ROOF
 INSULATION. PLEASE SHOW HOW YOU ARE ACHIEVING THE R-19
 INSULATION STATED IN THE ENERGY CALCULATIONS, WHEN THE
 WALLS IN THIS AREA DO NOT GO ALL THE WAY TO THE
 UNDERSIDE OF THE ROOF DECK.
 SEE 2017 ENERGY CODE COMMERCIAL. C402.5.9.1 VENTED
 DROPPED CEILING CAVITIES. WHERE VENTED DROPPED CEILING
 CAVITIES OCCUR OVER CONDITIONED SPACES, THE CEILING
 SHALL BE CONSIDERED TO BE BOTH THE UPPER THERMAL
 ENVELOPE AND PRESSURE ENVELOPE OF THE BUILDING AND
 SHALL CONTAIN A CONTINUOUS AIR BARRIER BETWEEN THE
 CONDITIONED SPACE AND THE VENTED UNCONDITIONED SPACE
 THAT IS ALSO SEALED TO THE AIR BARRIER OF THE WALLS.
 SEE THE DEFINITION OF AIR BARRIER IN SECTION C202.
 DEFINITION: AIR BARRIER. RELATING TO THE BUILDING
 ENVELOPE, AIR BARRIERS COMPRISE THE PLANES OF PRIMARY
 RESISTANCE TO AIRFLOW BETWEEN THE INTERIOR SPACES OF A
 BUILDING AND THE OUTDOORS AND THE PLANES OF PRIMARY
 AIRFLOW RESISTANCE BETWEEN ADJACENT AIR ZONES OF A
 BUILDING, INCLUDING PLANES BETWEEN ADJACENT CONDITIONED
 AND UNCONDITIONED AIR SPACES OF A BUILDING. TO BE
 CLASSED AS AN AIR BARRIER, A BUILDING PLANE MUST BE
 SUBSTANTIALLY LEAK FREE; THAT IS, IT SHALL HAVE AN AIR
 LEAKAGE RATE NOT GREATER THAN 0.5 CFM/FT2 WHEN
 SUBJECTED TO AN AIR PRESSURE GRADIENT OF 25 PASCAL. IN
 GENERAL, AIR BARRIERS ARE MADE OF DURABLE, NONPOROUS
 MATERIALS AND ARE SEALED TO ADJOINING WALL, CEILING OR
 FLOOR SURFACES WITH A SUITABLE LONG-LIFE MASTIC. HOUSE
 WRAPS AND TAPED AND SEALED DRYWALL MAY CONSTITUTE AN
 AIR BARRIER, BUT DROPPED ACOUSTICAL TILE CEILINGS
 (T-BAR CEILINGS) MAY NOT. BATT INSULATION FACINGS AND
 ASPHALT-IMPREGNATED FIBERBOARD AND FELT PAPER ARE NOT
 CONSIDERED AIR BARRIERS.
  
 4) SHEET A-2 DETAILS:
  
 4A) DETAIL # 6 SHOWS THE BREAK ROOM SINK BUT NOT THE
 REQUIREMENTS FOR:
 2017 FBC-ACCESSIBILITY CODE 606.4 FAUCETS. CONTROLS FOR
 FAUCETS SHALL COMPLY WITH 309. HAND-OPERATED METERING
 FAUCETS SHALL REMAIN OPEN FOR 10 SECONDS MINIMUM.
 2017 FBC-ACCESSIBILITY CODE 606.5 EXPOSED PIPES AND
 SURFACES. WATER SUPPLY AND DRAIN PIPES UNDER LAVATORIES
 AND SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO
 PROTECT AGAINST CONTACT. THERE SHALL BE NO SHARP OR
 ABRASIVE SURFACES UNDER LAVATORIES AND SINKS.
  
 4B) DETAIL #10 IS MISSING THE DISTANCE FROM THE WATER
 CLOSET TO THE TOILET PAPER DISPENSER. 2017 FBC-ACCESS.
 CODE 604.7 DISPENSERS. TOILET PAPER DISPENSERS SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
  
 4C) DETAIL # 10 ALSO NEEDS TO CORRECT THE HEIGHT OF THE
 GRAB BARS FOR THE WATER CLOSET. 2017 FBC-ACCESSIBILITY
 CODE SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS
 SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES
 MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 MEASURED TO THE TOP OF THE GRIPPING SURFACE, NOT
 CENTERLINE.
  
 5) IMPACT FEES- PAPER SUBMITTALS. PLANS REQUIRE REVIEW
 BY THE PBC IMPACT FEE OFFICE. CALL (561) 233-5025. UPON
 APPROVAL, YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO
 THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED AND
 WITH A COPY OF THE RECEIPT AS APPLICABLE. PLEASE
 PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 THE PBC IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC
 TFEES/FORMS/QUESTIONNAIRE.PDF
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  