| Plan Review Notes For Permit 19080122 |
| Permit Number |
19080122 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-08-11 08:56:43 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE CUT SHEETS FOR PRODUCT APPROVAL SHOWING UL | | | OR ORTHER NRTL LISTINGS OF ALL MATERIALS AND EQUIPMENT | | | TO BE USED ( RFID ANTENNA AND RFID READER) FBC 107.2.1 | | | NEC 90.7, 110.2, 110.3B | | | | | | 2. DOCUMENT HAS AN ENGINEER'S SEAL AND SIGNATURE BUT IT | | | NOT DIGITALLY SIGNED. PLAN SAYS DRAWN BY "CDH" CHECKED | | | BY "BMM". | | | | | | ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND | | | SIGNED/SEALED BY A DESIGN PROFESSIONAL OR THE | | | ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS | | | 471.003(2)(H); 471.025; WPB FBC 107.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-657-1653 | | | |
|