| 2019-09-13 15:25:11 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19080089 |
| | 9/13/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS M1 & M2: PROVIDE A SCOPE OF WORK FOR BUILDING |
| | 3 WITH KEYNOTES ON THE PLAN. IT APPEARS A NEW 5-TON AC |
| | SYSTEM IS BEING INSTALLED, AND NEW SUPPLY AND EXHAUST |
| | FANS- SECTION 107.1WPB. |
| | |
| | 2) M2: THE AC EQUIPMENT SCHEDULE FOR THE ADDITION |
| | INDICATES A RHEEM CONDENSER AND TRANE AIRHANDLER WHCH |
| | ARE MISMATCHED UNITS. PROVIDE A MATCHED SYSTEM OR |
| | CALCULATIONS AND SUPPORTING DATA FROM THE DESIGN |
| | PROFESSIONAL THAT DEMONSTRATES THE SYSTEM WILL MEET THE |
| | REQUIRED EFFICIENCY RATING- SECTION C403.2.3 FBC EC. |
| | |
| | 3) M1 & M2: SHOW HOW O/A IS BEING PROVIDED TO THE NEW |
| | AND EXISTING AIRHANDLERS IN THE ADDITION AND BUILDING |
| | 3- SECTION 401.2 FBC M. ACCORDING TO THE SCHEDULE THE |
| | NEW ADDITON SYSTEM IS PROVIDING 300 CFMS OF O/A AIR BUT |
| | NO O/A DUCT IS SHOWN. |
| | |
| | 4) M1 & M2: IT APPEARS BY THE PLAN THAT INADEQUATE |
| | MAKEUP AIR IS BEING PROVIDED FOR THE EXHAUST SYSTEMS. |
| | REFER TO SECTION 501.4 AND PROVIDE AIR BALANCE |
| | CALCULATIONS FOR THE NEW ADDITION AND BUILDING 3. |
| | |
| | 5) SHOW THE LOCATIONS OF THE NEW CONDENSERS AND PROVIDE |
| | INSTALLATION DETAILS- SEE SECTION 301.15 AND 301.16 FBC |
| | M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |