| Date |
Text |
| 2019-11-05 11:49:22 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. RISER DIAGRAM SHOWS #1 WIRE FEEDING A 200 AMP |
| | DISCONNECT AND PANEL. THIS WIRE IS NOT RATED FOR200 |
| | AMPS. IN ADDITION, THE LOAD CALCULATION SHOWS A LOAD OF |
| | 170 AMPS. THE #1 WIRE IS RATED FOR 130 AMPS. PROVIDE |
| | CORRECTION. NEC 310.15(B)(16); FBC RE E3603.1, E3705.1 |
| | 2. RISER DIAGRAM SHOWS A # 8 EQUIPMENT GROUNDING |
| | CONDUCTOR IN THE FEED FOR THE 200 AMP PANEL. THIS WIRE |
| | IS NOT SIZED PROPERLY, PROVIDE CORRECTION. NEC 250.122; |
| | FBC RE E3704.6, 3607.3.1 |
| | 3. OK |
| | 4. RISER DIAGRAM DOES NOT SHOW THE WIRE SIZE TO THE 60 |
| | AMP DISCONNECT. PROVIDE CORRECTION. NEC 215.5; FBC RE |
| | E3706.1, E3608.1, E3609.3; WPB FBC 107.2.1 |
| | 5. RISER DIAGRAM INDICATES THE 60 AMP DISCONNECT WILL |
| | BE FED FROM THE DUAL LUGS IN THE METER CAN. HOWEVER, |
| | THE LOAD IS SHOWN AS PART OF THE MAIN. WHERE IS THIS |
| | PANEL FED FROM? PROVIDE CLARIFICAITONS AND CORRECTIONS. |
| | WPB FBC 107.2.1 |
| | 6. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR |
| | SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE |
| | EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12 |
| | 7. THE MECHANICAL PLAN SHOWS THE NEW ROOM AS A DINING |
| | ROOM. IF SO, THE RECEPTACLE OUTLETS IN THIS ROOM ARE |
| | REQUIRED TO BE ON A SMALL APPLIANCE BRANCH CIRCUIT WITH |
| | A 20 AMP RATING AND WIRE SIZE. PROVIDE CORRECTION. NEC |
| | 210.52(B)(2); FBC RE E3703.2 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | PHIL PETTY |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6742 |
| | [email protected] |
| | |