Plan Review Notes
Plan Review Notes For Permit 19080055
Permit Number 19080055
Review Stop E
Sequence Number 1
Notes
Date Text
2019-08-21 13:59:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM SHOWS #1 WIRE FEEDING A 200 AMP
 DISCONNECT AND PANEL. THIS WIRE IS NOT RATED FOR200
 AMPS. IN ADDITION, THE LOAD CALCULATION SHOWS A LOAD OF
 170 AMPS. THE #1 WIRE IS RATED FOR 130 AMPS. PROVIDE
 CORRECTION. NEC 310.15(B)(16); FBC RE E3603.1, E3705.1
 2. RISER DIAGRAM SHOWS A # 8 EQUIPMENT GROUNDING
 CONDUCTOR IN THE FEED FOR THE 200 AMP PANEL. THIS WIRE
 IS NOT SIZED PROPERLY, PROVIDE CORRECTION. NEC 250.122;
 FBC RE E3704.6, 3607.3.1
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 4. RISER DIAGRAM DOES NOT SHOW THE WIRE SIZE TO THE 60
 AMP DISCONNECT. PROVIDE CORRECTION. NEC 215.5; FBC RE
 E3706.1, E3608.1, E3609.3; WPB FBC 107.2.1
 5. RISER DIAGRAM INDICATES THE 60 AMP DISCONNECT WILL
 BE FED FROM THE DUAL LUGS IN THE METER CAN. HOWEVER,
 THE LOAD IS SHOWN AS PART OF THE MAIN. WHERE IS THIS
 PANEL FED FROM? PROVIDE CLARIFICAITONS AND CORRECTIONS.
 WPB FBC 107.2.1
 6. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12
 7. THE MECHANICAL PLAN SHOWS THE NEW ROOM AS A DINING
 ROOM. IF SO, THE RECEPTACLE OUTLETS IN THIS ROOM ARE
 REQUIRED TO BE ON A SMALL APPLIANCE BRANCH CIRCUIT WITH
 A 20 AMP RATING AND WIRE SIZE. PROVIDE CORRECTION. NEC
 210.52(B)(2); FBC RE E3703.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved