| 2019-09-09 15:54:22 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19080055 |
| | REVIEWED: SEPTEMBER 9, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | 1) 107.5.3 FBC[AMENDED]THE TWO SETS OF DRAWINGS |
| | PROVIDED DO NOT MATCH. ONE SET INCLUDES REVISIONS AND |
| | THE OTHER DOES NOT. |
| | ALSO, SHEET S4 IS MISSING FROM THE SET WITHOUT |
| | REVISIONS. |
| | I?M REVIEWING THE SET WITH REVISIONS. |
| | |
| | 2) 501.1.1 FBC[RE] ADDITIONS, ALTERATIONS, OR REPAIRS: |
| | GENERAL. ADDITIONS, ALTERATIONS, OR REPAIRS TO AN |
| | EXISTING BUILDING, BUILDING SYSTEM OR PORTION THEREOF |
| | SHALL COMPLY WITH SECTION R502. UNALTERED PORTIONS OF |
| | THE EXISTING BUILDING OR BUILDING SUPPLY SYSTEM SHALL |
| | NOT BE REQUIRED TO COMPLY WITH THIS CODE. |
| | -PLEASE CHOOSE METHOD (R502.1.1, R502.1.2 OR |
| | R502.1.3)AND SUPPLY DOCUMENTAION TO COMPLY WITH THE |
| | METHOD CHOOSEN. |
| | |
| | 3) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR |
| | WINDOWS, MULL BAR AND DOORS W/SIDELITES IN ADDITION, OR |
| | INDICATE THAT YOU WOULD LIKE IT DEFERRED. |
| | |
| | 4) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR |
| | TILE ROOFING AND ADHESIVE, OR INDICATE THAT YOU WOULD |
| | LIKE IT DEFERRED. |
| | |
| | 5) 107.3.4.1 FBC[AMENDED] SUBMIT TRUSS SHOP DRAWINGS TO |
| | THE BUILDING INSPECTOR PRIOR TO INSTALLATION. |
| | - THE TRUSS SUBMITTAL CAN BE APPROVED NOW IF PUT IN |
| | SUPPORTING DOCUMENTS AS A SUBMITTAL, OR IT CAN BE |
| | DEFERRED. IF DEFERED THE TRUSS PACKAGE NEEDS TO BE |
| | REVIEWED BY BUILDING INSPECTOR PRIOR TO INSTALLATION. |
| | |
| | NOTES: |
| | |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |