| 2019-08-09 16:01:20 | 08/09/2019 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | |
| | 1. THE COPY OF SIGNATURE OR SEAL IS NOT IN ACCORDANCE |
| | WITH FLORIDA ADMINISTRATIVE CODE PER 61G15-23.001, |
| | FLORIDA STATUTE 471. PLEASE PROVIDE THE DOCUMENT FOR |
| | YOUR TIE DOWN WITHOUT A SEAL AND SIGNATURE, NO COPIES. |
| | |
| | 2. TABLE FOR NFPA IS NOT LEGIBLE, PLEASE PROVIDE COPIES |
| | THAT ARE NOT GRAYED OUT WHICH MAKE THE DIFFICULT TO |
| | READ, WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. SPECIFICATIONS FOR REGULATOR ARE DIFFICULT TO READ |
| | AS THEY ARE BLURRY AND FADED OUT, PLEASE PROVIDE CLEAR |
| | COPIES, IDENTIFY WHICH REGULATOR PLEASE, WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 4. THE LP TANK IS BELOW GROUND, PLEASE SHOW THE METHOD |
| | OF REQUIRED PROTECTION FOR THE LP TANK AND |
| | APPURTENANCES PER NFPA 58. THE TANK WILL NEED A COVER |
| | FOR VEHICLE TRAFFIC PROTECTION AS IT IS BELOW GROUND IT |
| | SHALL BE CONSTRUCTED AND PROTECTED PER NFPA 58 |
| | SEC.3-2.2.7 (H). WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 5. SHOW THE DEPTH OF THE LP GAS CONTAINER BELOW GRADE. |
| | COMPLY WITH NFPA 58 SEC. 6.6.6.1. |
| | |
| | 6. PLEASE SHOW UNION ON THE REGULATOR ON ISOMETRIC, |
| | UNION / 1' OF EITHER SIDE 2017 PBC FG SEC. 410.2 |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |