| 2019-10-11 17:24:22 | 10/11/19 2ND GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 2019 FLORIDA STATUTES |
| | TITLE XXXIII REGULATION OF TRADE, COMMERCE, |
| | INVESTMENTS, AND SOLICITATIONS |
| | CHAPTER 553 BUILDING CONSTRUCTION STANDARDS |
| | SECTION 80 ENFORCEMENT. |
| | |
| | 553.80 ENFORCEMENT. (B) WITH RESPECT TO EVALUATION OF |
| | DESIGN PROFESSIONALS' DOCUMENTS, IF A LOCAL GOVERNMENT |
| | FINDS IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH |
| | THE FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT |
| | DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE |
| | TIMES FOR FAILURE TO CORRECT A CODE VIOLATION |
| | SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION, |
| | INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION, |
| | STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING, |
| | VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS |
| | SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF |
| | THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO |
| | CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH |
| | TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED |
| | FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT |
| | OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS |
| | REVIEW. |
| | |
| | THERE SEEM TO BE A GAS PERMIT THIS IS YOU SECOND REVIEW |
| | AND FOR IT NOT TO GO TO THIRD PLEASE CONTACT ME OR SOME |
| | IN OUR OFFICE TO SEE IF WE CAN CORRECT THE FOLLOWING |
| | ITEMS; |
| | |
| | 1. UNDER THE AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | 6TH EDITION (2017), CHAPTER 1, ADMINISTRATION OF THE |
| | CITY WEST PALM BEACH SECTION 107.3.5.3 RESIDENTIAL ITEM |
| | 13 (ONE AND TWO-FAMILY). PLEASE SUBMIT AN GAS ISOMETRIC |
| | DRAWING THAT CLEARLY SHOWS THE LENGTH OF ALL CUT |
| | SECTIONS OF PIPE, WHERE YOUR METER IS LOCATED, HOW FAR |
| | THE DISTANCE, IS IT A 2LBS OR .05 LBS SYSTEM, LIST THE |
| | BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON |
| | THE SYSTEM, SHOWER UNION AND REGULATOR PER 2017 FBC |
| | FUEL GAS RES SECS. G2413.4.1, G2413.4.2. |
| | |
| | 2. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS |
| | PER THE 2017 FBC FUEL GAS RES. SEC. G2420.4. |
| | |
| | 3. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| | METER / MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE |
| | BUILDING AND/OR SYSTEM, LISTED SHUTOFF VALVES PER THE |
| | 2017 FBC FUEL GAS RES. SEC. G2413.4.1. |
| | |
| | 4. THE PLANS INDICATE AN EXISTING GAS METER. THE BTU |
| | LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE |
| | TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING |
| | SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING |
| | SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING |
| | SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS |
| | THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH |
| | APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH |
| | APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF |
| | PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES |
| | 2017 FBC FUEL GAS RES. SECS.G2412.4, G2412.8, G2413.1, |
| | G2413.2, G2413.3. |
| | |
| | 5. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 OR 2017 FBC |
| | FUEL GAS RES. SEC. G2421.1. |
| | |
| | 6. REGULATORS INSTALLED OUTDOORS SHALL BE DESIGNED, |
| | INSTALLED OR PROTECTED SO THEIR OPERATION WILL NOT BE |
| | AFFECTED BY THE ELEMENTS. PROVIDE DOCUMENTATION FROM |
| | THE MANUFACTURER THAT THE REGULATORS ARE APPROVED FOR |
| | EXTERIOR USE. NFPA 58-11 SEC. 6.8.1.5. |
| | |
| | 7. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE |
| | DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| | OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR |
| | ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| | SYSTEM 2017 FBC FUEL GAS RES. SEC. G2413.3. |
| | |
| | 8. THERE IS A FIRE PIT, SECOND TANKLESS AND POOL |
| | HEATER ON THE LAYOUT SUBMITTED AND NO SPECIFICATIONS OR |
| | INSTALLATION INSTRUCTION. AS NOTED IN ITEM 4 THERE IS A |
| | GAS METER ON THE MAIN HOUSE AND PERMIT 18090327 SHOW A |
| | RANGE, OUTDOOR GRILL AND 199 BTU?S TANKLESS WHICH IS |
| | NOT ADDED TO THE SYSTEM, PLEASE CLARIFY AND MAKE |
| | CORRECTION PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 105.1. |
| | |
| | 9. A SUB ELECTRICAL PERMIT IS REQUIRED FOR THE SOURCE |
| | OF IGNITION IF NOT THERE AT TIME OF INSTALLATION, WPB |
| | AMENDMENTS TO THE FBC SEC. 105.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 1:00 PM TO 4:00 PM |
| | [email protected] |
| | 561-805-6720 |
| | |