| 2019-08-05 14:51:32 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19071570 ROOFING SUB FOR MASTER |
| | #18060562 |
| | REVIEWED: AUGUST 5, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[B] = FBC BUILDING |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | |
| | [RAS 117]PROVIDE ENGINEERING FOR ENHANCED ATTACHMENT AS |
| | STATED IN PRODUCT APPROVAL UNDER GENERAL LIMITATIONS |
| | #11. ZONE 3 WILL EXCEED THE MAXIMUM DESIGN PRESSURE OF |
| | -67.5 AND THAT IS WHY ENGINEERING IS REQUIRED FOR THE |
| | MECHANICAL ATTACHMENT OF INSULATION IN THAT ZONE. |
| | ALSO, PROVIDE THE PRODUCT APPROVAL FOR THE INSULATION |
| | BOARDS WITH INSTALLATION INSTRUCTIONS. |
| | |
| | INFORMATIONAL: |
| | I REVIEWED PLANS AND ENERGY CALCULATIONS FROM MASTER |
| | PERMIT 18060562 TO SEE HOW INSULATION WAS PROVIDED, THE |
| | PLANS CALL FOR R-30 ABOVE THE DECK, BUT THE ENERGY |
| | CALCULATIONS CALL FOR R-19 BATT. PLEASE REVIEW AND |
| | REVISE THE PLANS OR ENERGY CALC FOR WHAT IS BEING |
| | INSTALLED IN 18060562. THIS COULD CAUSE THE BUILDING |
| | FINALS TO FAIL. |
| | |
| | NOTES: |
| | ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | |
| | WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |