| Date |
Text |
| 2019-08-12 07:24:59 | 08/12/2019 1ST PLUMBING/POOL REVIEW **DENIED** WITH |
| | COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. BACKFLOW PREVENTER REQUIRED PER THE CITY OF WEST |
| | PALM BEACH ORD #2853-95. A PERMIT REQUIRED BY A |
| | LICENSED CONTRACTOR AND MUST BE CERTIFIED BY UTILITIES |
| | PRIOR TO FINAL INSPECTION. A DUAL CHECK VALVE MAY BE |
| | USED IF NO POOL FILL IS INSTALLED AT THE METER AND |
| | INSTALLED BY UTILITIES WHICH DO NOT REQUIRE A PERMIT SO |
| | PLEASE CONTACT CITY OF WPB UTILITIES AT 561-822-2240 |
| | FOR FURTHER DIRECTIONS. |
| | 2. SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE |
| | MAXIMUM SYSTEM FLOW. IDENTIFY ON THE PUMP CURVE WHICH |
| | CURVE KEY IS SPECIFIC TO THE PUMP BEING INSTALLED ON |
| | THIS POOL. ). IT REQUIRES THAT THE MAXIMUM SYSTEM FLOW |
| | RATE DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF |
| | THE SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE |
| | TDH CALCULATIONS MUST INCLUDE ALL OF THE SYSTEM |
| | COMPONENTS INCLUDING SUCTION AND RETURN PIPING, |
| | FITTINGS, VALVES, HEATER, FILTER, AND CHLORINATOR. ALL |
| | SYSTEM COMPONENTS EXCEPT THE PUMP PER ANSI/APSP/ICC 7 - |
| | 2013 SECS. 4.4.9, 4.4.9.1. |
| | 3. INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS FOR |
| | THE PUMP BEING INSTALLED ON THIS SYSTEM. SUBMIT A POOL |
| | PUMP CURVE THAT IS ENLARGED, CLEAR IN DETAIL AND |
| | LEGIBLE PER WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 4. SUBMIT MANUFACTURE?S SPECIFICATION FOR PUMP AND |
| | CARTRIDGE FILTER THAT IS BEING USED PER WPB AMENDMENTS |
| | TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 1:00 PM TO 4:00 PM |
| | [email protected] |
| | 561-805-6720 |
| | |