Plan Review Notes
Plan Review Notes For Permit 19071501
Permit Number 19071501
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-08-01 15:18:45THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ALL UNDERGROUND FIRE LINE SHALL BE INSTALLED AND
 TESTED PER NFPA 24, STANDARD FOR THE INSTALLATION OF
 PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES,
 2013 EDITION
  
  
 2) PROVIDE ALL UNDERGROUND MANUFACTURES SPECIFICATIONS
 SHEETS FOR FIRE INSPECTOR REVIEW ON FIRE INSPECTION.
  
 PLEASE ENSURE COMPLIANCE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  