| Date |
Text |
| 2019-08-05 13:36:53 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19071411 |
| | ADD: 307 EVERNIA ST. SUITE: 200 |
| | CONT: 489 EXEMPT. NO WORK/ CHANGE OF OCCUPANCY |
| | TEL: 970-903-5721 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. AUGUST 05/ 2019 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-201: |
| | |
| | 1A) DISCREPANCIES IN THE PLAN, OCCUPANT LOADS: |
| | 1A)(1) ON THE LEFT SIDE OF THE PLAN THERE ARE 2 |
| | CLASSROOMS WITH 265 SQ. FT. OF CLASSROOM, ONE IS LARGER |
| | THAN THE OTHER AND ONE HAS 13 OCCUPANTS AND THE OTHER 6 |
| | OCCUPANTS. DISCREPANCY, 107.2.1.2. ADDITIONAL |
| | INFORMATION IS REQUIRED. IT APPEARS THIS MAYBE A STAFF |
| | AREA WITH SINK IN A BREAK ROOM? |
| | |
| | 1A)(2) THE CLASSROOM ON THE RIGHT SIDE OF THE SHEET |
| | INDICATES 275 SQ. FT. AND OCCUPANT LOAD OF 14. THE |
| | ACTUAL OCCUPANT LOAD IS 13.75, NEED TO BE ROUNDED DOWN |
| | TO THE NEXT WHOLE NUMBER SINCE THERE IS NO PARTS OF |
| | OCCUPANTS. TABLE 1004.1.2. |
| | |
| | 1A)(3) THERE IS NO OCCUPANT LOAD GIVEN FOR THE LIBRARY |
| | AT ALL. PLEASE REFER TO THE 2017 FBC-B TABLE |
| | 1004.1.2. |
| | |
| | 1A)(4) NO OCCUPANT LOADS HAVE BEEN GIVEN TO THE |
| | RECEPTION AREA, WAITING AREA NOR EXISTING STORAGE ROOM, |
| | OR THE FILE/ COPY ROOM. 107.2.1.2. ADDITIONAL |
| | INFORMATION IS REQUIRED. FBC-B TABLE 1004.1.2. |
| | |
| | 1B) THE PERMIT APPLICATION INDICATES THIS IS A CHANGE |
| | IN OCCUPANCY. SHEET A-201 INDICATES THAT THIS SPACE WAS |
| | USED AS A BUSINESS OCCUPANCY AND NOW IS TO BE A SCHOOL. |
| | PLEASE PROVIDE THE AGE OF THE STUDENTS THAT ARE GOING |
| | TO ATTENDING THIS SCHOOL SEE THE 2017 FBC-B SECTION |
| | 305.1 FOR AGE GROUP FOR AN EDUCATIONAL OCCUPANCY. |
| | |
| | 1C)UNDER THE HEADING OF APPLICABLE CODES LIST THE 2017 |
| | EXISTING BUILDING CODE, LEVEL I ALTERATION. FOR A |
| | CHANGE OF OCCUPANCY THE CODE REQUIRES US TO USE THE |
| | 2017 EXISTING BUILDING CODE CHAPTER 10 FOR CHANGE OF |
| | OCCUPANCY. SEE 2017 FBC-EXISTING BUILDING CODE SECTION |
| | 1001.2.2.1 PARTIAL CHANGE OF OCCUPANCY. |
| | WHERE THE OCCUPANCY CLASSIFICATION OR GROUP OF A |
| | PORTION OF AN EXISTING BUILDING IS CHANGED, SECTION |
| | 1012 SHALL APPLY. |
| | |
| | 1D) THE PLAN IS SILENT AS TO OCCUPANCY SEPARATION |
| | REQUIREMENTS UNDER THE 2017 FBC-EXISTING BUILDING CODE |
| | SECTIONS 1012.1.1 WITHOUT SEPARATION OR 1012.1.1.2 WITH |
| | SEPARATION. |
| | |
| | 1E) 2017 EXISTING BUILDING CODE 1012.1.3 CHANGE OF |
| | OCCUPANCY CLASSIFICATION BASED ON HAZARD CATEGORY. |
| | |
| | THE RELATIVE DEGREE OF HAZARD BETWEEN DIFFERENT |
| | OCCUPANCY CLASSIFICATIONS SHALL BE DETERMINED IN |
| | ACCORDANCE WITH THE CATEGORIES SPECIFIED IN TABLES |
| | 1012.4, 1012.5 AND 1012.6. SUCH A DETERMINATION SHALL |
| | BE THE BASIS FOR THE APPLICATION OF SECTIONS 1012.4 |
| | THROUGH 1012.7. |
| | PLEASE REVIEW IN THE 2017 EXISTING BUILDING CODE TABLE |
| | 1012.4. YOU ARE GOING FROM A HIGHER HAZARD CATEGORY |
| | FROM BUSINESS TO AN EDUCATIONAL OCCUPANCY. THE LOWER |
| | THE NUMBER THE HIGHER THE HAZARD. BUSINESS BEING A 4 |
| | TYPE HAZARD CATEGORY AND EDUCATIONAL BEING A 2 A HIGHER |
| | HAZARD CATEGORY. |
| | |
| | 1F) 2017 EXISTING BUILDING CODE 1012.2.2 FIRE ALARM AND |
| | DETECTION SYSTEM. WHERE A CHANGE IN OCCUPANCY |
| | CLASSIFICATION OCCURS OR WHERE THERE IS A CHANGE OF |
| | OCCUPANCY WITHIN A SPACE WHERE THERE IS A DIFFERENT |
| | FIRE PROTECTION SYSTEM THRESHOLD REQUIREMENT IN CHAPTER |
| | 9 OF THE FLORIDA BUILDING CODE, BUILDING THAT REQUIRES |
| | A FIRE ALARM AND DETECTION SYSTEM TO BE PROVIDED BASED |
| | ON THE NEW OCCUPANCY IN ACCORDANCE WITH CHAPTER 9 OF |
| | THE FLORIDA BUILDING CODE, BUILDING, SUCH SYSTEM SHALL |
| | BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF |
| | OCCUPANCY OCCURS. EXISTING ALARM NOTIFICATION |
| | APPLIANCES SHALL BE AUTOMATICALLY ACTIVATED THROUGHOUT |
| | THE BUILDING. WHERE THE BUILDING IS NOT EQUIPPED WITH A |
| | FIRE ALARM SYSTEM, ALARM NOTIFICATION APPLIANCES SHALL |
| | BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF |
| | OCCUPANCY OCCURS IN ACCORDANCE WITH SECTION 907 OF THE |
| | FLORIDA BUILDING CODE, BUILDING AS REQUIRED FOR NEW |
| | CONSTRUCTION. |
| | |
| | 1G) 2017 EXISTING BUILDING CODE 1012.1.4 ACCESSIBILITY. |
| | ALL BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY |
| | CLASSIFICATION SHALL COMPLY WITH SECTION 1012.8. |
| | 2017 EXISTING BUILDING CODE 1012.8 ACCESSIBILITY. |
| | EXISTING BUILDINGS THAT UNDERGO A CHANGE OF GROUP OR |
| | OCCUPANCY CLASSIFICATION SHALL COMPLY WITH THE |
| | PROVISIONS OF THE FLORIDA BUILDING CODE, ACCESSIBILITY. |
| | 2017 FBC-ACCESSIBILITY CODE 202.4.2 ACCESSIBLE FEATURES |
| | IN THE EVENT OF DISPROPORTIONALITY. WHEN THE COST OF |
| | ALTERATIONS NECESSARY TO MAKE THE PATH OF TRAVEL TO THE |
| | ALTERED AREA FULLY ACCESSIBLE IS DISPROPORTIONATE TO |
| | THE COST OF THE OVERALL ALTERATION, THE PATH OF TRAVEL |
| | SHALL BE MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE |
| | MADE ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE |
| | COSTS. IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO |
| | PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS |
| | THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING |
| | ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE |
| | ROUTE TO THE ALTERED AREA; (III) AT LEAST ONE |
| | ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX |
| | RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE |
| | DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL |
| | ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND |
| | ALARMS. |
| | |
| | 1H) 1012.4.1 MEANS OF EGRESS FOR CHANGE TO HIGHER |
| | HAZARD CATEGORY. |
| | |
| | WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A |
| | HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE |
| | 1012.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE |
| | REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING |
| | CODE, BUILDING. |
| | EXCEPTIONS: |
| | 1H)(1).STAIRWAYS SHALL BE ENCLOSED IN COMPLIANCE WITH |
| | THE APPLICABLE PROVISIONS OF SECTION 903.1. |
| | 2017 EXISTING BUILDING CODE SECTION 903.1 EXISTING |
| | SHAFTS AND VERTICAL OPENINGS. EXISTING STAIRWAYS THAT |
| | ARE PART OF THE MEANS OF EGRESS SHALL BE ENCLOSED IN |
| | ACCORDANCE WITH SECTION 803.2.1 FROM THE HIGHEST WORK |
| | AREA FLOOR TO, AND INCLUDING, THE LEVEL OF EXIT |
| | DISCHARGE AND ALL FLOORS BELOW. |
| | 1H)(2).EXISTING STAIRWAYS INCLUDING HANDRAILS AND |
| | GUARDS COMPLYING WITH THE REQUIREMENTS OF CHAPTER 9 |
| | SHALL BE PERMITTED FOR CONTINUED USE SUBJECT TO |
| | APPROVAL OF THE CODE OFFICIAL. |
| | 1H)(3).ANY STAIRWAY REPLACING AN EXISTING STAIRWAY |
| | WITHIN A SPACE WHERE THE PITCH OR SLOPE CANNOT BE |
| | REDUCED BECAUSE OF EXISTING CONSTRUCTION SHALL NOT BE |
| | REQUIRED TO COMPLY WITH THE MAXIMUM RISER HEIGHT AND |
| | MINIMUM TREAD DEPTH REQUIREMENTS. |
| | 1H)(4).EXISTING CORRIDOR WALLS CONSTRUCTED ON BOTH |
| | SIDES OF WOOD LATH AND PLASTER IN GOOD CONDITION OR |
| | 1/2- INCH-THICK (12.7 MM) GYPSUM WALLBOARD SHALL BE |
| | PERMITTED. SUCH WALLS SHALL EITHER TERMINATE AT THE |
| | UNDERSIDE OF A CEILING OF EQUIVALENT CONSTRUCTION OR |
| | EXTEND TO THE UNDERSIDE OF THE FLOOR OR ROOF NEXT |
| | ABOVE. |
| | 1H)(5).EXISTING CORRIDOR DOORWAYS, TRANSOMS AND OTHER |
| | CORRIDOR OPENINGS SHALL COMPLY WITH THE REQUIREMENTS IN |
| | SECTIONS 805.5.1, 805.5.2 AND 805.5.3. |
| | 1H)(6) .EXISTING DEAD-END CORRIDORS SHALL COMPLY WITH |
| | THE REQUIREMENTS IN SECTION 805.6. |
| | |
| | 2) 2017 FBC-B SPECIAL DETAILED REQUIREMENTS BASED ON |
| | USE AND OCCUPANCY. |
| | 401.1 DETAILED USE AND OCCUPANCY REQUIREMENTS. IN |
| | ADDITION TO THE OCCUPANCY AND CONSTRUCTION REQUIREMENTS |
| | IN THIS CODE, THE PROVISIONS OF THIS CHAPTER APPLY TO |
| | THE SPECIAL USES AND OCCUPANCIES DESCRIBED HEREIN. |
| | 401.2 ADDITIONAL DESIGN CRITERIA./ 401.2.1 SCOPE. |
| | 401.1 DETAILED USE AND OCCUPANCY REQUIREMENTS. IN |
| | ADDITION TO THE PROVISIONS OF THIS CHAPTER, THE |
| | FOLLOWING SPECIAL OCCUPANCIES, STANDARDS, REQUIREMENTS |
| | AND CODES SHALL CONFORM TO THE FOLLOWING SECTIONS: |
| | SECTION 468: SCHOOLS. |
| | |
| | 2A) 2017 FBC-B 468.3.2 GLARE FROM NATURAL LIGHT. |
| | SOURCES OF NATURAL LIGHT IN INSTRUCTIONAL SPACES SHALL |
| | BE GLAZED WITH GLARE REDUCING MATERIALS OR SHALL BE |
| | SHIELDED TO PREVENT GLARE THAT CAN INTERFERE WITH |
| | SEEING TASKS WITHIN THE INSTRUCTIONAL SPACE. |
| | 468.3.7.5 GLARE ELIMINATION. ILLUMINATION OF |
| | PERMANENTLY INSTALLED MARKERBOARDS, CHALKBOARDS, AND |
| | OTHER INSTRUCTION AIDS SHALL BE DESIGNED TO ELIMINATE |
| | GLARE AND SHADOWS. |
| | |
| | 2B) 468.3.5.5 WALLS. WALLS IN TOILET ROOMS SHALL BE |
| | IMPERVIOUS TO A HEIGHT OF AT LEAST 4 FEET (1219 MM) |
| | ABOVE THE FLOOR. |
| | |
| | 2C) 468.3.5.7.2 SOAP DISPENSERS FOR LIQUID, FOAM, OR |
| | POWDERED SOAP SHALL BE PROVIDED AT ALL HANDWASHING |
| | BASINS. |
| | |
| | 2D) 468.3.7.1 ILLUMINATION LEVEL IN |
| | CLASSROOMS/INSTRUCTIONAL SPACES. ILLUMINATION AT THE |
| | NORMAL TASK LEVEL FOR THE TYPE OF CLASSROOM/INSTRUCTION |
| | SPACE SHALL BE A MINIMUM OF 40 FOOTCANDLES (400 LUX). |
| | |
| | 2E) 468.3.7.2 ILLUMINATION UNIFORMITY IN CLASSROOMS/ |
| | INSTRUCTION SPACES. LUMINARIES SHALL HAVE A CEILING |
| | ARRANGEMENT OR BE POSITIONED AROUND THE WALLS SUCH THAT |
| | A UNIFORMED ILLUMINATION LEVEL, WITHIN 10 FOOTCANDLES |
| | (100 LUX), IS MAINTAINED AT THE STUDENTS REQUIRED |
| | NORMAL TASK LEVEL FOR THE TYPE OF CLASSROOM/INSTRUCTION |
| | SPACE. |
| | |
| | 2F) 468.3.7.3 BRIGHTNESS RATIO IN |
| | CLASSROOMS/INSTRUCTIONAL SPACES. THE BRIGHTNESS RATIO |
| | BETWEEN THE STUDENT TASK LEVEL AND THE INSTRUCTION AREA |
| | OR AREAS OR VISUAL DISPLAY LOCATION SHALL BE ONE TO |
| | FIVE OR LESS. |
| | |
| | 2G) 468.3.7.4 ILLUMINATION FAILURE OF GENERAL AND MEANS |
| | OF EGRESS LUMINARIES. ILLUMINATION SYSTEMS SHALL BE |
| | DESIGNED AND MAINTAINED SO THAT THE FAILURE OF ANY |
| | SINGLE LIGHTING UNIT, SUCH AS AN ELECTRIC LUMINARY, |
| | DOES NOT LEAVE ANY OCCUPIED SPACE OR MEANS OF EGRESS IN |
| | THE DARK. (SEE SECTION 1008 FOR ADDITIONAL MEANS OF |
| | EGRESS REQUIREMENTS.) |
| | |
| | 3) IMPACT FEES- PAPER SUBMITTALS. PLANS REQUIRE REVIEW |
| | BY THE PBC IMPACT FEE OFFICE. CALL (561) 233-5025. UPON |
| | APPROVAL, YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO |
| | THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED AND |
| | WITH A COPY OF THE RECEIPT AS APPLICABLE. PLEASE |
| | PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO |
| | THE PBC IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT: |
| | HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC |
| | TFEES/FORMS/QUESTIONNAIRE.PDF |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |