| Date |
Text |
| 2019-08-02 06:51:55 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. NO LOAD STUDY HAS BEEN PROVIDED PER NEC 220.87. |
| | PROVIDE LOAD STUDY OF EXISTING SERVICE. |
| | |
| | 2. "LOAD CALCULATION" PROVIDED DOES NOT SHOW |
| | CALCULATION FOR NEW LOAD ONLY SHOWS "250AMPS" ADDED. |
| | PROVIDE LOAD CALCULATION SHOWING ADDITION OF NEW LOAD. |
| | FBC 107.2.1 NEC 220. |
| | |
| | 3. SPECIFY LOCATION OF ELECTRICAL DATUM PLANE IN |
| | RELATION TO HEIGHT OF DOCK/PIER FBC 107.2.1 |
| | |
| | 4 GROUND FAULT PROTECTION REQUIRED FOR NEW CIRCUIT |
| | BREAKER FOR FEEDER THAT'S TO BE INSTALLED IN MSB. NEC |
| | 555.3 |
| | |
| | 5 SPECIFY HEIGHT OF NEW JBOX TO BE INSTALLED. FBC |
| | 107.2.1 NEC 555.9 |
| | |
| | 6 PROVIDE CUT SHEETS FOR PRODUCT APPROVAL OF PEDESTALS |
| | AND PROPOSED PORTABLE POWER CABLES. FBC 107.2.1 NEC |
| | 90.7, 110.2, 110.3B |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |
| | |