| Plan Review Notes For Permit 19071347 |
| Permit Number |
19071347 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-07-31 10:30:39 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC B 107.2.1 PLEASE PROVIDE CONNECTION DETAILS | | | INCLUDING FRAMING, SHEATHING, AND DRYWALL. | | | | | | NOTE: ANY CONNECTORS/FASTENERS IN CONTACT WITH PRESSURE | | | TREATED MATERIAL SHALL BE COMPATIBLE AS PER FBC B | | | 2304.10.5. |
|