2019-08-07 15:00:15BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19071321
 REVIEWED: AUGUST 7, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[RE] = FBC ENERGY CONSERVATION
  
 1) 109.3 FBC[AMENDED] PROJECT VALUE APPEARS LOW.
 PLEASE PROVIDE COPY OF PROPOSAL WITH CONTRACTOR TO SHOW
 WORK VALUE EQUAL TO THE AMOUNT SHOWN ON PERMIT
 APPLICATION, OR PROVIDE ESTIMATE TO SHOW ANTICIPATED
 COSTS.
  
 2) 401.2 FBC[RE] PROVIDE ENERGY CALCULATIONS TO MEET
 REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE. CHOOSE
 METHOD IN R401.2 AND SUPPLY DOCUMENTATION.
 -PLEASE SUPPLY ENERGY CALCULATIONS WITH CHECKLISTS AND
 EPL CARD.
 2A) HOW IS CEILING INSULATED? PLEASE INCLUDE IN THE
 ENERGY CALCULATIONS.
  
 3) WIND DESIGN CRITERIA.
 RISK CATEGORY = ___(II)
 EXPOSURE CATEGORY = ___(B,C OR D)
 BUILDING CLASSIFICATION = __________(ENCLOSED)
 MEAN BLDG. HGT. = ___FT. ___IN.(TOP OF ROOF DECK)
 WIND SPEED V ULT = _____(170)
 WIND SPEED V ASD = _____(132)
 DESIGN PRESSURE FOR EACH OPENING = +___ & -___
 ZONE OF OPENING = (4 OR 5?)
  
 WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  