| 2019-08-05 14:56:58 | 1) SHOW THE POOL PIPING LAYOUT ON THE PLANS. WPB AMEND. |
| | TO FBC SEC. 107.2.1. |
| | 2) THE SPECIFICATION ON THE PLAN FOR THE AQUASTAR |
| | CHANNEL DRAIN IS BLURRED AND BARELY LEGIBLE. SUBMIT A |
| | CLEAR AND LEGIBLE DETAIL. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 3) SUBMIT AN EXPANDED AND LEGIBLE PUMP CURVE FOR THE |
| | JET PUMP FOR REVIEW. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 4) THE PLANS REFER TO THE 2006 EDITION OF APSP - 7. THE |
| | 2013 EDITION OF APSP 7 HAS BEEN ADOPTED PER THE 2017 |
| | FBC-BUILDING. |
| | 5) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE |
| | MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM |
| | ITS PUMP CURVE AND THE SIMPLIFIED TOTAL DYNAMIC HEAD |
| | CALCULATION IS NO LONGER ALLOWED TO BE USED IN |
| | DETERMINING MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC |
| | 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 EDITION |
| | ADDRESSES FLOW RATE IN GALLONS PER MINUTE (GPM). IT |
| | REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED |
| | THE LISTED MAXIMUM FLOW RATE OF THE SUCTION OUTLET |
| | FITTING ASSEMBLY (DRAIN COVER).THE TDH CALCULATIONS |
| | MUST INCLUDE ALL OF THE SYSTEM COMPONENTS INCLUDING |
| | SUCTION AND RETURN PIPING, FITTINGS, VALVES, HEATER, |
| | FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS EXCEPT |
| | THE PUMP. |
| | 6) IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS |
| | SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL. THIS |
| | IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE |
| | TDH CALCULATIONS. ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, |
| | 4.4.9.1 |
| | 7) A BACKFLOW IS REQUIRED ON THE AUTOFILL PER 2017 |
| | FBC-PLUMBING SEC.608.1. |
| | 8) A REDUCED PRESSURE ZONE BACKFLOW DEVICE WILL BE |
| | REQUIRED AT THE WATER METER PER THE CITY OF WEST PALM |
| | CROSS CONNECTION CONTROL MANUAL. |
| | 9) THE PLANS SHOW DUAL SUCTION OUTLETS ON THE SWIMMING |
| | POOL. DUAL OUTLETS SHALL BE SEPARATED BY A MINIMUM OF 3 |
| | FEET PER APSP 7-2013 SEC.5.3.1. |
| | 10) THE FLOW RATE FOR THE RECIRCULATION PUMP LISTED IN |
| | THE BOX UNDER "ANSI-7/15" AT THE LISTED TDH DOES NOT |
| | CORRELATE WITH PUMP CURVE FOR THE FLOW RATE AND TDH |
| | SHOWN ON THE CURVE. CLARIFY. |
| | 11) THE POOL HEATER SHALL HAVE A MIMIMUM THERMAL |
| | EFFICIENCY OF 82% PER THE 2017 FBC-ENERGY SEC. |
| | R403.10.4. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |